GCP5000 (GCE) INSTALLATION, CALIBRATION AND SYSTEM OPERATIONAL CHECK
_________________________________________________________________________________________________________
6-11
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
4.
To start the calibration press the “1” key.
Figure 6-10 Start Calibration
5.
The Display will show the following asking the user to press the S1 button on the PSO
module to be calibrated. After pressing the button on the module, press OK on the
display to continue (within 60s)
Figure 6-11 Calibration Confirmation Screen
6.
The display will show:
•
Initiating …
•
In Progress ….
•
Passed or Failed displayed for 30s when the island calibration is complete
•
Calibrated (if Passed)
•
When Passed or Calibrated appears, continue to Step 3. If Failed appears, see
the following WARNING.