SSCC APPLICATIONS & PROGRAMMING GUIDELINES
_________________________________________________________________________________________________________
4-31
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
4.11.5.3 Example 3 - Crossing Configured for Two GP Inputs (One to Each SSCC)
This example is the same as example 2 except that one GP input is assigned to each SSCC
Module. To configure the crossing to respond to a gate position (GP) input to each crossing
controller:
•
In the SSCC Configuration window set
SSCC1+2
GP Coupled
to
Yes
. This will
cause the lamps on both crossing controllers to flash if either GP input goes low
•
In the SSCC 1 Configuration window set the
SSCC-1 Number of GPs
to 1 (default).
•
In the SSCC 2 Configuration window set the
SSCC-2 Number of GPs
to 1.
•
Assign GP 1.1 to an input, by default this is already assigned to IN 7.5.
•
Assign GP 2.1 to an input, for example IN 8.5.
4.11.5.4 Example 4 - Crossing Configured With GP Inputs To Independent SSCCs
The crossing controllers may be configured to function with minimum interaction, thus allowing
each SSCC module to independently control lamp activation. This typically may be used on
divided highways where a single gate malfunction does not affect opposing traffic. To configure
the crossing controllers for independent operation:
In the SSCC Configuration window set
SSCC1+2
GP Coupled
to
No
.
In the SSCC 1 Configuration window set the
SSCC-1 Number of GPs
to 1 (default).
In the SSCC 2 Configuration window set the
SSCC-2 Number of GPs
to 1.
Assign GP 1.1 to an input, by default this is already assigned to IN 7.5.
Assign GP 2.1 to an input, for example IN 8.5.
When the GP input to SSCC 1 de-energizes, only the lamps controlled by SSCC-1 flash. When
the GP input to SSCC 2 de-energizes, only the lamps controlled by SSCC-2 flash
4.11.5.5 Example 5 - Crossing Configured for Flashers Only Using One SSCC Module
The crossing controllers may be configured to only operate the crossing flashers. To configure
the crossing controllers for this function:
•
On the Module Selection menu set
SSCC-2 Slot
to
Not Used
•
On the SSCC Configuration menu set the
Gates Used
to
No