GCP5000 (GCE) INSTALLATION, CALIBRATION AND SYSTEM OPERATIONAL CHECK
__________________________________________________________________________________________
6-20
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
•
Flashing
indicates that the SSCC IIIi module
lamp outputs are alternately energizing
(flashing).
•
Failed
indicates that a bell, lamp, or crossing gate output failure has been detected.
6.4.2 GCP5000 (GCE) Operational Test Mode
Before placing a system in service, tests must be performed to verify proper system operation
and I/O wiring. Proceed to the next step if a feature is not used.
WARNING
AFTER INITIAL PROGRAMMING OR SUBSEQUENT PROGRAMMING,
MODULE, TRACK, OR WIRING CHANGES, TESTS MUST BE
PERFORMED TO VERIFY THE PROPER OPERATION OF THE GCE
PRIOR TO PLACING THE SYSTEM IN SERVICE.
WARNING
ANY TIME THE TRAIN IS MOVING WITHIN THE APPROACH LIMITS,
TRACK DISCONTINUITY CAUSED BY A HIGH RESISTANCE BOND OR
A DEFECTIVE COUPLER IS INDICATED. LOCATE AND CORRECT THE
PROBLEM IMMEDIATELY.
THE RAILROAD PROCEDURES GOVERNING HOW TO TAKE A TRACK
CIRCUIT OUT OF SERVICE SHALL BE FOLLOWED ONLY IF ALLOWED
BY THE RAILROAD