DETAILED CASE AND MODULE DESCRIPTION
_________________________________________________________________________________________________________
8-21
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
Table 8-11 Diagnosing PSO Module Problems
The following table shows the diagnostic messages generated by the PSO Module.
Diag Display /
Description
Cause
Remedy
PSO Receiver 1
Recovering
(Diag7001)
PSO Receiver 1 Out of Service
The PSO Receiver runs a 30s recovery
timeout after an error has cleared
PSO Receiver 1 Out
of Service
(Diag7002)
PSO Receiver 1 Out of Service
If the PSO receiver is not meant to be out of
service, use the display module or out of
service inputs (if used) to put the PSO
receiver back into service
PSO Receiver 1
Recovering
(Diag7001)
PSO receiver 1 is recovering from
a health error
Wait for 30s, if the error does not reoccur,
then this will clear
PSO Receiver 1 Out
of Service
(Diag7002)
PSO Receiver 1 is out of service
Information only.
PSO Receiver 1
Frequency Error
(Diag7003)
The PSO Receiver 1 frequency has
not been set
Select the frequency specified on the site
plans from the GCP Programming menu
PSO Receiver 1
Calibrating
(Diag7004)
PSO Receiver 1 is currently
calibrating
Wait a minute for calibration to complete.
PSO Receiver 1
Calibration Error
(Diag7005)
PSO Receiver 1 failed calibration
a) Check that the receiver is configured
properly in the Program menu.
b) Check the physical connections.
c) Replace the module.
PSO Receiver 1
Sample Error
(Diag7006)
PSO Receiver 1 hardware error in
the receiver
If the problem persists replace the module
PSO Receiver 1
Wrong Code
(Diag7007)
PSO Receiver 1 receiving an
unexpected code
PSO Receiver 1 is detecting a code it is not
configured to accept check plans and field
wiring.