SSCC APPLICATIONS & PROGRAMMING GUIDELINES
_________________________________________________________________________________________________________
4-28
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
Table 4-6 SSCC GD Input Selection
NUMBER SELECTED IN
CORRESPONDING GDs
FIELD
SSCC-1 VITAL INPUT
SELECTION AVAILABLE
SSCC-2 VITAL INPUT
SELECTION AVAILABLE
0
Not Used
Not Used
1
Not Used
GD 1.1
Not Used
GD 2.1
2
Not Used
GD 1.1
GD 1.2
Not Used
GD 2.1
Gd 2.2
3
Not Used
GD 1.1
GD 1.2
GD 1.3
Not Used
GD 2.1
GD 2.2
GD 2.3
4
Not Used
GD 1.1
GD 1.2
GD 1.3
GD 1.4
Not Used
GD 2.1
GD 2.2
GD 2.3
GD 2.4
4.11.4.5 Flash Rate
•
The rate in flashes per minute at which the lamps flash.
•
The range is 30 to 70 flashes per minute, in steps of 5 flashes.
•
Default:
50
4.11.4.6 Low Battery Detection
•
When set to Yes the controller monitors its battery.
•
The maintenance call output drops when a low battery condition is detected.
•
Default:
No
4.11.4.6.1 Low Battery Level
•
Displays when Low Battery Detection is set to
Yes
•
Sets the low battery detection level.
•
If the controller detects a battery voltage lower than this value it will log a low battery
detected and activate the maintenance call output.
•
Range: 90 – 150dV (9.0 – 15.0 volts DC). Default:
90dV
(9.0 volts)
4.11.4.7 Flash Sync
•
Used to synchronize all flashing lights.
•
External controllers can be synchronized with the flash sync output of the CPU
connector.
•
A crossing controller can be designated as either master or slave.
SSCC1Default:
master
SSCC2 Default:
slave