Commissioning
5.6 Commissioning with STARTER
Control Units CU240S
96
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
5.6.2
Series Commissioning with STARTER
Upload a parameter set with STARTER
Prerequisites
● An inverter with an apropriate parameter set is available (upload inverter)
● STARTER is installed on the PC used for series commissioning
● Supply voltage is active for the upload inverter
● The upload inverter is in "Ready to Run".
Connect the STARTER PC via the Option Port(USS on RS232, peer to peer)to the upload
inverter (PC connection Kit requiered), press the online button
and perform the upload by
activating the button
.
Note
Upload with STARTER to MMC or BOP
If you want to upload a parameter set with STARTER to an MMC or a BOP, P0010, P0802
must be set via the expert list.
Download a parameter set with STARTER
Prerequisites
● Supply voltage is active for the download inverter
● The download inverter is in "Ready to Run".
Connect the STARTER PC via the Option Port (USS on RS232, peer to peer) to the
download inverter (PC connection Kit requiered), press the online button
and perform the
download by activating the button . The data set must be saved in the EEPROM.
Note
Download with STARTER to MMC or BOP
If you want to perform an manual download of a parameter set with STARTER from an MMC
or a BOP, P0010, P0803 and P0804 must be set via the expert list.