Communication
6.2 Cyclic Communication
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
135
6.2.5
Control and status words
Description
The control and status words comply with the specifications for PROFIdrive Profile, version
4.1 for "Closed-loop speed control mode".
Control word 1 (STW1)
Control word 1 (bits 0 … 10 as per PROFIdrive Profile and VIK/NAMUR, bits 11 … 15
specific to SINAMICS G120).
Table 6-17 Assignment control word 1
Bit Val.
Meaning
comment
P0922 =
20
(VIK/
NAMUR)
P0922 = 1 / 350
/ 352 / 353 / 354
(PROFI
drive Profile)
0
OFF1
Shutdown, deceleration along RFG ramp, pulse disable when f < f
min
.
0
1
ON
Sets the inverter to the "Ready to run" state, direction of rotation must
be defined via bit 11.
P0840 = 2090:0 P0840 = 2090:0
0
Coast Stop (OFF2)
Instantaneous pulse disable, drive coasts to a standstill
1
1
No Coast Stop
All Coast Stop (OFF2) commands are withdrawn.
P0844 = 2090:1 P0844 = 2090:1
0
Quick Stop (OFF3)
Rapid stop: Shutdown at fastest possible acceleration rate.
2
1
No Quick Stop
All Quick Stop (OFF3) commands are withdrawn.
P0848 = 2090:2 P0848 = 2090:2
0
Disable Operation
Closed-loop control and inverter pulses are disabled
3
1
Enable Operation
Closed-loop control and inverter pulses are enabled
P0852 = 2090:3 P0852 = 2090:3
0
Reset Ramp Generator
Output of RFG is set to 0 (fastest possible braking operation), inverter
remains in the ON state.
4
1
Enable Ramp Generator
P1140 = 2090:4 P1140 = 2090:4
0
Freeze Ramp Generator
Setpoint currently supplied by the RFG is "frozen".
5
1
Unfreeze Ramp Generator
P1141 = 2090:5 P1141 = 2090:5
0
Disable Setpoint
Value selected at the RFG input is set to 0.
6
1
Enable Setpoint
Value selected at the RFG input is activated.
P1142 = 2090:6 P1142 = 2090:6
7
1
Fault Acknowledge
Fault is acknowledged with a positive edge, inverter then switches to
"starting lockout" state.
P1024 = 2090:7 P1024 = 2090:7