Commissioning
5.6 Commissioning with STARTER
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
95
5.6.1
Single Commissioning with STARTER
STARTER projects
Using STARTER either a new project can be created or an already existing project can be
opened.
To create a new project in STARTER one of the following methods can be used:
● Search inverter
● Wizard
● Select inverter
When opening an existing project or creating a new project STARTER is in the offline mode.
To go online the button
has to be pressed.
Changing parameters with STARTER
Parameters can be changed online or offline (online preferred).
Online parameter changes are stored in the RAM of the inverter. A manual transfer from
RAM to EEPROM can be triggered by pressing the button
. When closing STARTER and
the contents of the RAM and EEPROM are different, the user is asked whether or not they
wish to transfer the RAM data to the EEPROM.
Parameter sets that have been changed offline can be transferred to the inverter using the
download button.
CAUTION
If you use fail-safe applications, pay attention to the following note:
•
Parameters for fail-safe functions can only be changed in the online mode.
When downloading parameters via STARTER, parameters belonging to fail-safe
functions will not be downloaded.