Description
3.5 Factory Settings of the Control Unit
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
27
Table 3-4
Command sources and their BICO connections with default settings of P0700
CU240S (P0700 = 2)
CU240S DP (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter
BICO source
Parameter
BICO source
ON/OFF1 / ON/OFF1
P0840 = 722.0
DI0
P0840 = 2090.0
CW1, Bit 0
ON reverse/OFF1 (not active per default)
P0842 = 0.0
---
P0842 = 0.0
---
First OFF2 source: Coast stop
P0844 = 1.0
---
P0844 = 2090.1
CW1, Bit 1
Second OFF2 source: Coast stop
P0845 = 19.1
BOP
P0845 = 19.1
BOP
First OFF3 source: Quick stop
P0848 = 1.0
---
P0848 = 2090.2
CW1, Bit 2
Second OFF3 source: Quick stop
P0849 = 1.0
---
P0849 = 1.0
---
Pulse enable
P0852 = 1.0
---
P0852 = 2090.3
CW1, Bit 3
Table 3-5
Fixed frequency command sources and their BICO connections with default settings of P0700
CU240S (P0700 = 2),
CU240S DP (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter
BICO source
Parameter
BICO source
Fixed freq. selection Bit 0
P1020 = 722.3
DI3
P1020 = 722.3
DI3
Fixed freq. selection Bit 1
P1021 = 722.4
DI4
P1021 = 722.4
DI4
Fixed freq. selection Bit 2
P1022 = 722.5
DI5
P1022 = 722.5
DI5
Fixed freq. selection Bit 3
P1023 = 722.6
DI6
P1023 = 0
---
Table 3-6
Monitoring settings and their BICO connections with default settings of P0700
CU240S (P0700 = 2)
CU240S DP (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter
BICO source
Parameter
BICO source
First source for "Fault acknowledge"
P2103 = 722.2
DI2
P2103 = 722.2
DI2
Second source for "Fault acknowledge"
(not active per default)
P2104 = 0.0
---
P2104 = 2090.7
CW1, Bit 7
External fault
P2106 = 1
---
P2106 = 1
---
Table 3-7
Factory settings for setpoint source
CU240S (P0700 = 2)
CU240S DP (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S PN-F (P0700 = 6)
Source
Parameter
BICO source
Parameter
BICO source
Frequency setpoint
r0754[0], [%]
AI0+ / AI0-
P2050.1 [Hex]
PZD from Fieldbus