Commissioning
5.5 Commissioning using the BOP
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
57
5.5.1.2
Changing Parameters via BOP
Changing parameter with the BOP
The description below serves as an example that shows how to change any parameter using
the BOP.
Table 5-4
Changing P0003 - parameter access level
Step
Result on display
1 Press
to access parameters
2 Press
until P0003 is displayed
3 Press
to display the parameter value
4 Press
or
to set the required value (set to 3)
5 Press
to confirm and store the value
6 All level 1 to level 3 parameters are now visible to the user.
Table 5-5
Changing P0700 an index parameter - setting BOP control
Step
Result on display
1 Press
to access parameters
2 Press
until P0700 is displayed
3 Press
to access the parameter value
4 Press
or
to select index 1
5 Press
to display actual set value
6 Press
or
to the required value
7 Press
to confirm and store the value
8 Press
until r0000 is displayed
9 Press
to return the display to the standard drive display (as defined by the customer)
Note
The BOP sometimes displays "bUSY" when changing parameter values. This means that the
inverter is presently handling another higher-priority task.