Troubleshooting
8.4 Troubleshooting via the Control System
Control Units CU240S
200
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
8.4
Troubleshooting via the Control System
Diagnostics using diagnostic parameters
The following diagnostic parameters are set via a higher-level control system. This function
is provided by Control Units, which communicate via PROFINET or PROFIBUS.
Identification of the communications components
The read-only parameter r2053 shows the information by which the various firmware
components of the PROFIBUS DP interface can be identified.
Table 8-2
Identification of communications firmware
Parameter
Meaning
0: Inverter cannot identify the communications interface
1: PROFIBUS DP detected
2: Not assigned
r2053.00
56: Undefined communications error
r2053.01
Firmware version
r2053.02
Constant "0"
r2053.03
Firmware date (year)
r2053.04
Firmware date (day and month)
Standard diagnostics
When the parameter P2041.03 = 0, then by using the read-only parameter r2054 and it’s
indices, it is possible to obtain detailed diagnostic information regarding the PROFIBUS DP
interface. This information is listed in the table below.
Table 8-3
Standard diagnostics
Parameter
Meaning
PROFIBUS DP status:
0: Off
1: Baud rate search
2: Baud rate found
3: Cyclical data exchange
r2054.00
(> 100: other diagnostic screen active)
r2054.02
Number of acyclical links with class 2 master (PC, BOP): 0 … 2
r2054.03
Error number of last unsuccessful parameter access operation through an acyclical
link.
r2054.04
Parameter number of last unsuccessful parameter access operation
r2054.05
Sub-index of last unsuccessful parameter access operation
When parameter accessing errors occur, r2054.03 display the appropriate error number,
these are listed in table below.