Appendix
A.3 EMC Overall Performance
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
211
A.3
EMC Overall Performance
EMC Emissions
The SINAMICS G120 drives have been tested in accordance with the emission requirements
of the category C2 (domestic) environment.
Table A-1
Conducted & Radiated Emissions
EMC Phenomenon
Standard
Level
Conducted Emissions
EN 55011
Class A
Radiated Emissions
EN 55011
Class A
Note
To achieve this performance the default switching frequency should not be exceeded.
In order to achieve conducted emissions to EN 55011 Class B there is a range of PM240
external filter options available.
Achieving radiated emissions to EN 55011 Class B is largely dependent on the drive being
correctly installed inside a metallic enclosure. The limits will not be met if the drive is not
enclosed or installed in accordance with good EMC practices.
Harmonic Currents
The harmonic current emissions from the SINAMICS G120 drives is as follows:
Table A-2
Harmonic Currents
Rating
Typical Harmonic Current (% of rated input current)
5th
7th
11th
13th
17th
19th
23rd
25th
FSA … FSF
(400 V, 370 W … 110 kW)
73
52
25
23
22
15
12
10
Note
Units installed within the category C2 (domestic) environment require connection to the
public low-voltage power supply network. Please contact your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.