Operating Instructions
Chapter
5
Flexi Soft Gateways
8012664/XB29/2013-06-11
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
85
Subject to change without notice
Ethernet gateways
5.4.1
Interfaces and operation
The FX0-GPNT is equipped with an integrated 3-port switch for connection with the Ether-
net network. Two RJ-45 sockets are available for the connection. The switch functionality
allows the FX0-GPNT to be used for connection to another Ethernet component (e.g. con-
nection to a notebook) without having to interrupt the Ethernet connection to the network.
LED
Meaning
No power supply
PWR
Green
Power supply switched on
No Ethernet connection
Green
Ethernet connection active, no data transmission
LINK/ACT 1
LINK/ACT 2
Green
Ethernet connection active, data transmission
Power-up
Green
Executing (live process data from/to FX3-CPUx)
Green 1
Hz:
Idle
2 Hz: PROFINET master requested LED flashing for
physical device identification
Red
1 Hz: Configuring/configuration required
2 Hz: Critical fault on gateway
Red
Critical fault on another module
STATUS
Red/green Executing, but Ethernet communication not established
or faulty (can be switched off, see below)
Error elimination is described in section 5.4.7 “Diagnostics and troubleshooting” on
page 100.
Fig. 39: Interfaces and
display elements of the
FX0
>
GPNT
Tab. 66: Meaning of the LED
displays of the FX0-GPNT
Symbol description:
: LED is off
Green: LED lights up green
Red: LED flashes red
Note
RJ
>
45 Ethernet socket
RJ
>
45 Ethernet socket
LED power supply (green)
LED network activity for Ethernet
port 1 or 2 (green)
LED STATUS (red/green)