Ethernet gateways
5.5.10
Diagnostics and troubleshooting
The FX0-GETC provides the following module status bits in the Flexi Soft system for diag-
nostic purposes. The module number of the FX0-GETC is 16.
Bit
Error message
Possible causes
0
Module not in operation
No process data connection with the PLC
1
Module has internal error
Hardware error. Replace module
2
Module has external error
No process data connection with the PLC
3
Reserved n/a
4
Configuration invalid or
incompatible
The configuration of the Flexi Soft system is
invalid, e.g. a hardware component has
been added or removed or has been
replaced by an incompatible device
5
Module input status invalid
No process data connection with the PLC
Configuration required or in progress
EtherCAT status is Pre-operational or less
6
Module output status invalid
No process data connection with the PLC
EtherCAT status is Safe-operational or less
7 … 31
Reserved n/a
Tab. 81: Module status bits