Fieldbus gateways
How to set the DeviceNet address via hardware address switches:
Set the DeviceNet address using the hardware address switches on the device front.
Then switch the Flexi Soft system off and back on again.
Switch
Function
× 10
Address switch 1
10 position rotary switch for setting the module address (ones)
× 1
Address switch 2
10 position rotary switch for setting the module address (ones)
The module addresses that can be selected using the address switches are in the
range 1-63.
If both address switches on the device are set to 0, then the address configured in
Flexi Soft Designer is used. There the address can be set in the range 0-63.
If a higher address is selected, address 63 is active.
How to set the baud rate via hardware DIP switches:
Set the baud rate using the DIP switches on the device. Then switch the Flexi Soft
system off and back on again.
Baud rate [kbit/s]
DIP 1
DIP 2
DIP 3
DIP 4
125
On On On Off
250
Off On On Off
500
On Off On Off
If all DIP switches are set to Off, then the setting for the baud rate in Flexi Soft Designer
is used.
All other DIP switch settings will set the baud rate to 125 kbit/s.
How to set the DeviceNet address and baud rate via software using the Flexi Soft
Designer:
Set both address switches to 0.
Set all DIP switches to Off.
Open the Flexi Soft Designer and load the hardware configuration including the
DeviceNet gateway. Ensure that your project is offline.
Click on the
Gateways
button above the main window and select the FX0-GDEV or
double click the FX0-GDEV in the hardware configuration view to open the gateway
configuration dialog.
Click on
Gateway configuration
on the left hand menu. The following dialog will be
displayed:
Tab. 134: Address switches
on the FX0-GDEV
Notes
Fig. 75: DIP switch settings
on the FX0-GDEV
Tab. 135: DIP switch settings
on the FX0-GDEV
Notes
Baud rate (kbit/s)
500
250