3.3.4
Routing of data from a second network
If your Flexi Soft system contains two gateways, it is possible to rout information received
by the first gateway from one network (e.g. from a Modbus PLC) into a second network via
the second gateway (e.g. to a PROFIBUS master) and vice versa.
3.3.5
Configuration checksums (CRCs)
Data set 2 contains the following configuration CRCs for the Flexi Soft system:
overall CRC (same as system CRC). The overall CRC is the checksum displayed in the
Flexi Soft Designer report.
system CRC (SCID)
verified configuration CRC. If this value is identical to the System CRC, the configuration
is verified. Otherwise the configuration is not verified.
Each checksum is four bytes long. Data set 2 can not be customized.
3.3.6
Error and status information of the modules
Data set 3 contains the module status information transferred to the network.
Four bytes are transferred for each module (e.g. FX3-XTIO). Data set 3 can not be
customized.
Reserved (for future use) = static 1 (no status change)
If no module is present, all values including the reserved values are set to logical 1.
The four status bytes for each module are being transferred in Big Endian format as
32 bit word, i.e. the most significant byte (MSB = byte 3) is transferred first and the
least significant byte (LSB = byte 0) is transferred last.
Module status bits of the FX3-CPUx main modules
The module status bits have the following significance, if not otherwise stated:
0 = Error
1 = No error
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
EFI2 EFI1 Power
supply
Configuration
Flexi Soft system
Reserved
Summary of
bits 0.5 to 0.7
(power supply
and EFI)
Internal tests
Module
operating state
1 = Run
0 = Other
Byte 1
Reserved
Flexi Link stations
suspended
1 = None
0 = One or more
Flexi Link stations
in the system
1 = All found
0 = One or more
are missing
Byte 2
Reserved
Byte 3
Reserved
Tab. 8: Module status bits of the FX3-CPUx main modules