Fieldbus gateways
The following table matches the module specific diagnostics data to the appropriate error
message.
Module no.
(M1)
Diagnostics bit
(M2 … M5)
Emergency
origin
Emergency message
00
Operating state Run
01
Internal tests
02
Summary of bits 05 to 07
03
Reserved
04
Configuration Flexi Soft system
05
Power supply
06
EFI1
07
EFI2
08
Flexi Link stations in the system
1 = All found
0 = One or more are missing
09
Flexi Link stations suspended
1 = None
0 = One or more
01
10 … 31
CPU
Reserved
00
Operating state Run
01
Internal tests
02
Summary of bits 05 to 07
03
Reserved
04
Configuration of this module is valid
05
Outputs power supply
06
Output
Fast-Shut-Off
07
Reserved
08
Input 1-2 dual channel input evaluation
09
Input 3-4 dual channel input evaluation
10
Input 5-6 dual channel input evaluation
11
Input 7-8 dual channel input evaluation
12 … 15
Reserved
16
External test signal Input 1
17
External test signal Input 2
18
External test signal Input 3
19
External test signal Input 4
20
External test signal Input 5
21
External test signal Input 6
22
External test signal Input 7
23
External test signal Input 8
24
Short-circuit monitoring output 1: short-circuit to high
25
Short-circuit monitoring output 1: short-circuit to low
26
Short-circuit monitoring output 2: short-circuit to high
27
Short-circuit monitoring output 2: short-circuit to low
28
Short-circuit monitoring output 3: short-circuit to high
29
Short-circuit monitoring output 3: short-circuit to low
30
Short-circuit monitoring output 4: short-circuit to high
02
31
XTIO/XTDI
Short-circuit monitoring output 4: short-circuit to low
00
Operating state Run
01
Internal tests
02
Summary of bits 05 to 07
03
Reserved
04
Configuration of this module is valid
05
Communication from the network
06
Communication to the network
03
07 … 31
PROFIBUS
gateway
Reserved
00
Operating state Run
01
Internal tests
02
Summary of bits 05 to 07
03
Reserved
04
Configuration of this module is valid
05
Communication from the network
04
06
CANopen
gateway
Communication to the network
Tab. 105: CANopen