I.3
Date Code 20170814
Instruction Manual
SEL-700G Relay
M
IRRORED
B
ITS
Communications
Operation
Table I.3 shows an example of the values of the M
IRRORED
B
ITS
for a
RXDFLT setting of 10100111.
Individual pickup and dropout security counters supervise the movement of
each received data bit into the corresponding RMBn element. You can set each
pickup/dropout security counter from 1 to 8. A setting of 1 causes a security
counter to pass every occurrence, while a setting of 8 causes a counter to wait
for eight consecutive occurrences in the received data before updating the data
bits. The pickup and dropout security count settings are separate. Control the
security count settings with the settings RMBnPU and RMBnDO.
A pickup/dropout security counter operates identically to a pickup/dropout
timer, except that the counter uses units of counted received messages instead
of time. Select a setting for the security counter in accordance with the
transmission rate (see Table I.1). For example, when transmitting at 2400 bps,
a security counter set to 2 counts delays a bit by about 30 ms. However, when
operating at 9600 bps, a setting of 2 counts delays a bit by about 8.5 ms.
You must consider the impact of the security counter settings in the receiving
relay to determine the channel timing performance, particularly when two
relays of different processing rates are communicating via M
IRRORED
B
ITS
,
such as an SEL-321 and an SEL-700G. The SEL-321 processes power system
information each 1/8 power system cycle, but, when transmitting at
19200 bps, the SEL-700G processes M
IRRORED
B
ITS
messages at 4.15 ms at
60 Hz (4 times per power system cycle at 60 Hz). Although the SEL-321
processes power system information each 1/8 power system cycle, the relay
processes the M
IRRORED
B
ITS
pickup/dropout security counters as M
IRRORED
B
ITS
messages are received. Because the SEL-700G transmits messages at
approximately 1/4-cycle processing interval (9600 bps and above, see
Table I.1), a counter set to two in the SEL-321 delays a received bit by another
approximately 1/2 cycle. However, a security counter in the SEL-700G with a
setting of two delays a received bit from the SEL-321 by 1/4 cycle, because
the SEL-700G is receiving new M
IRRORED
B
ITS
messages each 1/8 cycle
from the SEL-321.
Channel
Synchronization
When an SEL-700G detects a communications error, it deasserts ROKA or
ROKB. If an SEL-700G detects two consecutive communications errors, it
transmits an attention message, which includes the TXID setting. The relay
transmits an attention message until it receives an attention message that
includes a match to the TXID setting value. If the attention message is
successful, the relay has properly synchronized and data transmission
resumes. If the attention message is not successful, the relay repeats the
attention message until it is successful.
Table I.2
Positions of the M
IRRORED
B
ITS
Bit/
Row
7
6
5
4
3
2
1
0
88
RMB8A
RMB7A
RMB6A
RMB5A
RMB4A
RMB3A
RMB2A
RMB1A
90
RMB8B
RMB7B
RMB6B
RMB5B
RMB4B
RMB3B
RMB2B
RMB1B
Table I.3
M
IRRORED
B
ITS
Values for a RXDFLT Setting of 10100111
Bit/
Row
7
6
5
4
3
2
1
0
88
1
0
1
0
0
1
1
1
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...