F.25
Date Code 20170814
Instruction Manual
SEL-700G Relay
IEC 61850 Communications
Logical Nodes
PY1PTOV3
Op.general
59PY1T
Y-Side, Level 1 phase overvoltage element trip
PY1PTOV3
Str.general
59PY1
Y-Side, Level 1 phase overvoltage element pickup
PY1PTOV3
Str.dirGeneral
unknown
Direction undefined
PY1PTUV3
Op.general
27PY1T
Y-Side, Level 1 phase undervoltage element trip
PY1PTUV3
Str.general
27PY1
Y-Side, Level 1 phase undervoltage element pickup
PY1PTUV3
Str.dirGeneral
unknown
Direction undefined
PY2PIOC7
Op.general
50PY2T
Y-Side, Level 2 phase instantaneous overcurrent element trip
PY2PIOC7
Str.general
50PY2P
Y-Side, Level 2 phase instantaneous overcurrent element pickup
PY2PIOC7
Str.dirGeneral
unknown
Direction undefined
PY2PTOC6
Op.general
67PY2T
Y-Side, Level 2 phase directional overcurrent trip
PY2PTOC6
Str.general
67PY2P
Y-Side, Level 2 phase directional overcurrent pickup
PY2PTOC6
Str.dirGeneral
unknown
Direction unknown due to settings
PY2PTOV4
Op.general
59PY2T
Y-Side, Level 2 phase overvoltage element trip
PY2PTOV4
Str.general
59PY2
Y-Side, Level 2 phase overvoltage element pickup
PY2PTOV4
Str.dirGeneral
unknown
Direction undefined
PY2PTUV4
Op.general
27PY2T
Y-Side, Level 2 phase undervoltage element trip
PY2PTUV4
Str.general
27PY2
Y-Side, Level 2 phase undervoltage element pickup
PY2PTUV4
Str.dirGeneral
unknown
Direction undefined
PYAPIOC8
Op.general
50PY3AT
Y-Side, Level 3 Phase A instantaneous overcurrent element trip
PYAPIOC8
Str.general
50PY3AP
Y-Side, Level 3 Phase A instantaneous overcurrent element pickup
PYAPIOC8
Str.dirGeneral
unknown
Direction undefined
PYBPIOC9
Op.general
50PY3BT
Y-Side, Level 3 Phase B instantaneous overcurrent element trip
PYBPIOC9
Str.general
50PY3BP
Y-Side, Level 3 Phase B instantaneous overcurrent element pickup
PYBPIOC9
Str.dirGeneral
unknown
Direction undefined
PYCPIOC10
Op.general
50PY3CT
Y-Side, Level 3 Phase C instantaneous overcurrent element trip
PYCPIOC10
Str.general
50PY3CP
Y-Side, Level 3 Phase C instantaneous overcurrent element pickup
PYCPIOC10
Str.dirGeneral
unknown
Direction undefined
PYPTOC10
Op.general
51PYT
Y-side phase time overcurrent element trip
PYPTOC10
Str.general
51PYP
Y-side, phase time overcurrent element pickup
PYPTOC10
Str.dirGeneral
unknown
Direction unknown due to settings
Q1PIOC21
Op.general
46Q1T
Negative-sequence definite-time overcurrent element timed out
Q1PIOC21
Str.general
46Q1
Negative-Sequence Level 1 instantaneous overcurrent element pickup
Q1PIOC21
Str.dirGeneral
unknown
Direction undefined
Q2PIOC22
Op.general
46Q2T
Negative-sequence time-overcurrent element timed out
Q2PIOC22
Str.general
46Q2
Negative-sequence overcurrent element pickup
Q2PIOC22
Str.dirGeneral
unknown
Direction undefined
QX1PIOC17
Op.general
50QX1T
X-Side, Level 1 negative-sequence instantaneous overcurrent element
trip
Table F.16
Logical Device: PRO (Protection)
(Sheet 8 of 11)
Logical Node
Attribute
Data Source
Comment
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...