![background image](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-700g-series/sel-700g-series_instruction-manual_1216730382.webp)
SET.6
of 68
SEL-700G Relay
Instruction Manual
Date Code 20170814
SEL-700G Settings Sheets
Group Settings (SET Command)
LVL2 INV-TM CURV (0.5, 1, 1.0, 2, 2.0) (Hidden if 24CCS := OFF, DD, or U)
24IC :=
LVL2 INV-TM FCTR (0.1–10.0
S
) (Hidden if 24CCS := OFF, DD, or U)
24ITD :=
LVL2 PICKUP 1 (100–200 %) (Hidden if 24CCS := OFF, ID, I, or U)
24D2P1 :=
LVL2 TIME DLY 1 (0.04–400.00 s) (Hidden if 24CCS := OFF, ID, I, or U)
24D2D1 :=
LVL2 PICKUP 2 (101–200 %) (Hidden if 24CCS := OFF, I, or U)
24D2P2 :=
LVL2 TIME DLY 2 (0.04–400.00 s) (Hidden if 24CCS := OFF, I, or U)
24D2D2 :=
LVL2 RESET TIME (0.00–400.00 s) (Hidden if 24CCS := OFF)
24CR :=
24 ELEM TRQCTRL (SEL
OGIC
)
24TC :=
Out of Step Element
(Hidden if Slot E = Empty/71/ 75 or Slot Z = 83/87)
OUT-OF-STEP PROT (N, 1B, 2B)
E78 :=
(All Out of Step settings are hidden if E78 := N is selected)
FORWARD REACH (0.1–100.0 ohm [5 A I
XNOM
], 0.5–500.0 ohm [1 A I
XNOM
])
78FWD :=
REVERSE REACH (0.1–100.0 ohm [5 A I
XNOM
], 0.5–500.0 ohm [1 A I
XNOM
])
78REV :=
RIGHT BLINDER (0.1–50.0 ohm [5 A I
XNOM
], 0.5–250.0 ohm [1 A I
XNOM
])
(Hidden if E78 := 2B)
78R1 :=
LEFT BLINDER (0.1–50.0 ohm [5 A I
XNOM
], 0.5–250.0 ohm [1 A I
XNOM
])
(Hidden if E78 := 2B)
78R2 :=
OUTER BLINDER (0.2–100.0 ohm [5 A I
XNOM
], 1.0–500.0 ohm [1 A I
XNOM
])
(Hidden if E78 := 1B)
78R1 :=
INNER BLINDER (0.1–50.0 ohm [5 A I
XNOM
], 0.5–250.0 ohm [1 A I
XNOM
])
(Hidden if E78 := 1B)
78R2 :=
OOS DELAY (0.00–1.00 s) (Hidden if E78 := 1B)
78D :=
OOS TRIP DELAY (0.00–1.00 s)
78TD :=
OOS TRIP DUR (0.00–5.00 s)
78TDURD :=
POS-SEQ CURRENT (0.25–30.00 A [5 A I
XNOM
], 0.05–6.00 A [1 A I
XNOM
])
50ABC :=
OOS TRQCTRL (SEL
OGIC
)
OOSTC :=
Inadvertent Energization
(Shown if Slot Z = 81/82/85/86)
INADV ENRG EN (Y, N)
EINAD :=
(All Inadvertent Energization settings are hidden if EINAD := N)
GEN DE-ENRG PU (0.00–100.00 s)
GENDEPU :=
GEN DE-ENRG DO (0.00–100.00 s) (GENDEDO > INADPU)
GENDEDO :=
INADV ENRG PU (0.00–10.00 s) (GENDEDO > INADPU)
INADPU :=
INADV ENRG DO (0.00–10.00 s)
INADDO :=
INADV TRQCTRL (SEL
OGIC
)
INADTC :=
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...