F.34
SEL-700G Relay
Instruction Manual
Date Code 20170814
IEC 61850 Communications
Logical Nodes
Table F.18 shows the LN associated with control elements defined as Logical
Device CON.
Table F.19 shows the LN associated with annunciation elements defined as
Logical Device ANN.
THERMMTHR1
MaxOthTmp.instMag.f
RTDOTHMX
c
Other maximum RTD temperature
THERMMTHR1
Tmp01.instMag.f–
Tmp12.instMag.f
RTD1–RTD12
c
RTD1–RTD12 temperature
Functional Constraint = ST
THERMMTHR1
EEHealth.stVal
RTDFLT?1:3
c
RTD input or communication status
a
MX values contain instantaneous attributes (instMag) and instCVal), which are updated whenever the source updates and other attributes
which are only updated when the source foes outside the data source’s deadband (mag and cVal). Only the instantaneous values are shown
in the table.
b
Data validity depends on the relay model and installed card options. Refer to Section 1: Introduction and Specifications for different relay
models of available card options. Refer to Section 5: Metering and Monitoring for the model dependent metering quantities.
c
Valid data depends on E49RTD and RTD1LOC–RTD12LOC.
Table F.17
Logical Device: MET (Metering)
(Sheet 7 of 7)
Logical Node
Attribute
Data Source
Comment
Table F.18
Logical Device: CON (Remote Control)
Logical Node
Status
Control
Relay Word Bit
Comment
RBGGIO1
SPCSO01.stVal–
SPCSO08.stVal
SPCSO01.Oper.ctlVal–
SPCSO08.Oper.ctlVal
RB01–RB08
Remote Bits RB01–RB08
RBGGIO2
SPCSO09.stVal–
SPCSO16.stVal
SPCSO09.Oper.ctlVal–
SPCSO16.Oper.ctlVal
RB09–RB16
Remote Bits RB09–RB16
RBGGIO3
SPCSO17.stVal–
SPCSO24.stVal
SPCSO17.Oper.ctlVal–
SPCSO24.Oper.ctlVal
RB17–RB24
Remote Bits RB17–RB24
RBGGIO4
SPCSO25.stVal–
SPCSO32.stVal
SPCSO25.Oper.ctlVal–
SPCSO32.Oper.ctlVal
RB25–RB32
Remote Bits RB25–RB32
Table F.19
Logical Device: ANN (Annunciation)
(Sheet 1 of 5)
Logical Node
Attribute
Data Source
Comment
Functional Constraint = DC
DevIDLPHD1
PhyNam.model
PARTNO
Part number
Functional Constraint = MX
a
AINCGGIO21
AnIn01.instMag.f–
AnIn04.instMag.f
AI301–AI304
b
Analog Inputs (AI301 to AI304)—Slot C
AINDGGIO22
AnIn01.instMag.f–
AnIn04.instMag.f
AI401–AI404
b
Analog Inputs (AI401 to AI404)—Slot D
AINEGGIO23
AnIn01.instMag.f–
AnIn04.instMag.f
AI501–AI504
b
Analog Inputs (AI501 to AI504)—Slot E
BWXASCBR1
AbrPrt.instMag.f
WEARAX
X Breaker–Contact A wear
BWXBSCBR2
AbrPrt.instMag.f
WEARBX
X Breaker–Contact B wear
BWXCSCBR3
AbrPrt.instMag.f
WEARCX
X Breaker–Contact C wear
BWYASCBR4
AbrPrt.instMag.f
WEARAY
Y Breaker–Contact A wear
BWYBSCBR5
AbrPrt.instMag.f
WEARBY
Y Breaker–Contact B wear
BWYCSCBR6
AbrPrt.instMag.f
WEARCY
Y Breaker–Contact C wear
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...