IEC 61850 Operation
custom data models. Instead of having to look up data in a profile stored in its
database, an IEC 61850 client can simply query an IEC 61850 device and
receive a description of all logical devices, logical nodes, and available data.
Unlike other Supervisory Control and Data Acquisition (SCADA) protocols
that present data as a list of addresses or indices, IEC 61850 presents data with
descriptors in a composite notation made up of components. Table F.2 shows
how the A-phase current expressed as MMXU$A$phsA$cVal is broken down
into its component parts.
Data Mapping
Device data are mapped to IEC 61850 logical nodes (LN) according to rules
defined by SEL. Refer to IEC 61850-5:2003(E) and IEC 61850-7-4:2003(E)
for the mandatory content and usage of these LNs. The SEL-700G logical nodes
are grouped under Logical Devices for organization based on function. See
Table F.3 for descriptions of the Logical Devices in an SEL-700G. See Logical
Nodes for a description of the LNs that make up these Logical Devices.
MMS
Manufacturing Messaging Specification (MMS) provides services for the
application-layer transfer of real-time data within a substation LAN. MMS
was developed as a network independent data exchange protocol for industrial
networks in the 1980s and standardized as ISO 9506.
In theory, you can map IEC 61850 to any protocol. However, it can be
unwieldy and quite complicated to map objects and services to a protocol that
only provides access to simple data points via registers or index numbers.
MMS supports complex named objects and flexible services that enable
mapping to IEC 61850 in a straightforward manner. This was why the UCA
users group used MMS for UCA from that start, and why the IEC chose to
keep it for IEC 61850.
GOOSE
The Generic Object Oriented Substation Event (GOOSE) object within IEC
61850 is for high-speed control messaging. IEC 61850 GOOSE automatically
broadcasts messages containing status, controls, and measured values onto the
network for use by other devices. IEC 61850 GOOSE sends the messages several
times, increasing the likelihood that other devices receive the messages.
Table F.2
Example IEC 61850 Descriptor Components
Components
Description
MMXU
Logical Node
Polyphase measurement unit
A
Data Object
Phase-to-ground amperes
PhsA
Sub-Data Object
Phase A
cVal
Data Attribute
Complex value
Table F.3
SEL-700G Logical Devices
Logical Device
Description
ANN
Annunciator elements—alarms, status values
CFG
Configuration elements—datasets and report control blocks
CON
Control elements—Remote bits
MET
Metering or Measurement elements—currents, voltages, power, etc.
PRO
Protection elements—protection functions and breaker control
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...