SET.15
of 68
Date Code 20170814
Instruction Manual
SEL-700G Relay
SEL-700G Settings Sheets
Group Settings (SET Command)
FREQX ROC DO DLY (0.00–60.00 s) (Hidden if 81RX2TP := OFF)
81RX2DO :=
FREQX ROC LEVEL (OFF, 0.10–15.00 Hz/s) (Hidden if E81RX < 3)
81RX3TP :=
FREQX ROC TREND (INC, DEC, ABS) (Hidden if 81RX3TP := OFF)
81RX3TRN :=
FREQX ROC PU DLY (0.10–60.00 s) (Hidden if 81RX3TP := OFF)
81RX3TD :=
FREQX ROC DO DLY (0.00–60.00 s) (Hidden if 81RX3TP := OFF)
81RX3DO :=
FREQX ROC LEVEL (OFF, 0.10–15.00 Hz/s) (Hidden if E81RX < 4)
81RX4TP :=
FREQX ROC TREND (INC, DEC, ABS) (Hidden if 81RX4TP := OFF)
81RX4TRN :=
FREQX ROC PU DLY (0.10–60.00 s) (Hidden if 81RX4TP := OFF)
81RX4TD :=
FREQX ROC DO DLY (0.00–60.00 s) (Hidden if 81RX4TP := OFF)
81RX4DO :=
FREQX ROC VSUPER (OFF, 12.5–300.0 V)
81RXVSUP :=
FREQX ROC TRQCTRL (SEL
OGIC
)
81RXTC :=
Y-Side Rate-of-Change-of-Frequency Elements
(Shown if Slot E = 71/ 75)
ENABLE 81RY (N, 1–4)
E81RY :=
(All Y-Side Rate-of-Change-of-Frequency settings are hidden if E81RY := N)
FREQY ROC LEVEL (OFF, 0.10–15.00 Hz/s)
81RY1TP :=
FREQY ROC TREND (INC, DEC, ABS) (Hidden if 81RY1TP := OFF)
81RY1TRN :=
FREQY ROC PU DLY (0.10–60.00 s) (Hidden if 81RY1TP := OFF)
81RY1TD :=
FREQY ROC DO DLY (0.00–60.00 s) (Hidden if 81RY1TP := OFF)
81RY1DO :=
FREQY ROC LEVEL (OFF, 0.10–15.00 Hz/s) (Hidden if E81RY < 2)
81RY2TP :=
FREQY ROC TREND (INC, DEC, ABS) (Hidden if 81RY2TP := OFF)
81RY2TRN :=
FREQY ROC PU DLY (0.10–60.00 s) (Hidden if 81RY2TP := OFF)
81RY2TD :=
FREQY ROC DO DLY (0.00–60.00 s) (Hidden if 81RY2TP := OFF)
81RY2DO :=
FREQY ROC LEVEL (OFF, 0.10–15.00 Hz/s) (Hidden if E81RY < 3)
81RY3TP :=
FREQY ROC TREND (INC, DEC, ABS) (Hidden if 81RY3TP := OFF)
81RY3TRN :=
FREQY ROC PU DLY (0.10–60.00 s) (Hidden if 81RY3TP := OFF)
81RY3TD :=
FREQY ROC DO DLY (0.00–60.00 s) (Hidden if 81RY3TP := OFF)
81RY3DO :=
FREQY ROC LEVEL (OFF, 0.10–15.00 Hz/s) (Hidden if E81RY < 4)
81RY4TP :=
FREQY ROC TREND (INC, DEC, ABS) (Hidden if 81RY4TP := OFF)
81RY4TRN :=
FREQY ROC PU DLY (0.10–60.00 s) (Hidden if 81RY4TP := OFF)
81RY4TD :=
FREQY ROC DO DLY (0.00–60.00 s) (Hidden if 81RY4TP := OFF)
81RY4DO :=
FREQY ROC VSUPER (OFF, 12.5–300.0 V)
81RYVSUP :=
FREQY ROC TRQCTRL (SEL
OGIC
)
81RYTC :=
X-Side Frequency Accumulators
(Hidden if Slot Z = 83/84/87/88)
ENABLE FREQ ACC (N, 1–6)
E81ACC :=
(All Frequency Accumulators settings are hidden if E81ACC := N)
FREQ ACC DELAY (0.00–400.00 s)
62ACC :=
BAND1 UPPER LIMIT (15.00–70.00 Hz)
UBND1 :=
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...