5.22
SEL-700G Relay
Instruction Manual
Date Code 20170814
Metering and Monitoring
Breaker Monitor
25 Percent to 50 Percent Breaker Wear
Refer to Figure 5.22. The current value changes from 2.5 kA to 12.0 kA. 12.0
kA is interrupted 11 times (11 close/open operations = 24 – 13), pushing the
breaker maintenance curve from the 25 percent wear level to the 50 percent
wear level.
Compare the 100 percent and 50 percent curves. Note that for a given current
value, the 50 percent curve has only 1/2 of the close/open operations of the
100 percent curve.
Figure 5.22
Breaker Monitor Accumulates 50 Percent Wear
10,000
100%
1000
2
3
4
5
6
7
8
9
100
2
3
4
5
6
7
8
9
10
2
3
4
5
6
7
8
9
1
2
3
4
5
6 7 8 9
50
40
30
20
10
.5
Number of Close/Open Operations
kA Interrupted per Operation
25%
50%
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...