8.17
Date Code 20170814
Instruction Manual
SEL-700G Relay
Front-Panel Operations
Operation and Target LEDs
Table 8.5
SEL-700G and SEL-700G1 Front-Panel Operator Control Functions
Continually press the
LOCK
operator control pushbutton for three (3) seconds to engage/
disengage the lock function (Latch LT01 functions as Lock with the latch in reset state
equivalent to the engaged lock). While this pushbutton is pressed, the corresponding LED
flashes on and off, indicating a pending engagement or disengagement of the lock func-
tion. The LED illuminates constantly to indicate the engaged state. While the lock func-
tion is engaged, the following operator control is “locked in position” (assuming factory-
default settings):
CLOSE
.
While “locked in position,” this operator control cannot change state if pressed—the
corresponding LEDs remain in the same state. When the lock function is engaged, the
CLOSE
operator control cannot close
GEN BRKR
(generator breaker), but the
TRIP
operator
control can still trip
GEN BRKR
. Note that the
LOCK ENABLED
condition results in the
BLOCK
CLOSE
LED coming ON.
Press the
AUX
operator control pushbutton to enable/disable user-programmed auxiliary
control. The corresponding LED can be programmed to illuminate during the enabled
state.
NOTE:
The
AUX
operator control does not perform any function with the factory-default
settings.
Press the
CLOSE
operator control pushbutton to close
GEN BRKR
. The corresponding
GEN
BRKR CLOSED
LED illuminates to indicate that the breaker is closed.
Option: Set a delay, so that the operator can press the
CLOSE
operator control pushbut-
ton and then move a safe distance away from the breaker before the SEL-700G0, -1
issues a close (the
CLOSE
operator control comes with no set delay in the factory set-
tings). With a set delay, press the
CLOSE
operator control pushbutton momentarily, and
notice that the
BRKR CLOSED
LED flashes on and off during the delay time, indicating a
pending close. Abort the pending close by pressing the
CLOSE
operator control push-
button again or by pressing the
TRIP
operator control pushbutton. This delay setting
for the
CLOSE
operator control is SV03PU (range: 0 to 3000 seconds; factory set at 0—
no delay). The delay is set via the SET L command. See Table 4.57 for more
information.
Press the
TRIP
operator control pushbutton to trip the GEN BRKR (and take the control to
the lockout state). The
GEN
BRKR OPEN
LED illuminates to indicate that the breaker is
open.
Option: Set a delay, so that the operator can press the
TRIP
operator control pushbutton
and then move a safe distance away from the breaker before the SEL-700G0, -1
issues a trip (the
TRIP
operator control comes with no set delay in the factory settings).
With a set delay, press the
TRIP
operator control pushbutton momentarily and notice
that the
GEN BRKR OPEN
LED flashes on and off during the delay time, indicating a
pending trip. Abort the pending trip by pressing the
TRIP
operator control pushbutton
again or by pressing the
CLOSE
operator control pushbutton. This delay setting for the
TRIP
operator control is SV04PU (range: 0 to 3000 seconds; factory-set at 0—no
delay). The delay is set via the SET L command. See Table 4.57 for more
information.
ENABLED
LOCK
DISABLED
AUX
GEN BRKR CLOSED
CLOSE
BLOCK CLOSED
GEN BRKR OPEN
TRIP
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...