3-20
Distance and Overcurrent Elements
Date Code 20011205
SEL-311A Instruction Manual
Figure 3.14: Phase Time-Overcurrent Element 51PT
Accuracy
Pickup:
±
0.05 A secondary and
±
3% of setting (5 A nominal phase current inputs, IA, IB, IC)
±
0.01 A secondary and
±
3% of setting (1 A nominal phase current inputs, IA, IB, IC)
Curve Timing:
±
1.50 cycles and
±
4% of curve time for currents between (and including)
2 and 30 multiples of pickup
51PT Element Logic Outputs
The logic outputs in Figure 3.14 are the Relay Word bits shown in Table 3.4.