11-6
Front-Panel Interface (Only on Models with LCD)
Date Code 20011205
SEL-311A Instruction Manual
F
UNCTIONS
U
NIQUE TO THE
F
RONT
-P
ANEL
I
NTERFACE
Two front-panel primary functions do not have serial port command equivalents. These are:
·
Local control (accessed via the CNTRL pushbutton)
·
Modified rotating display with scroll lock control (accessed via the OTHER pushbutton)
Local Control
Use local control to enable/disable schemes, trip/close breakers, etc., via the front panel.
In more specific terms, local control asserts (sets to logical 1) or deasserts (sets to logical 0) what
are called local bits LB1 through LB16. These local bits are available as Relay Word bits and
are used in SEL
OGIC
®
control equations (see Rows 5 and 6 in Tables 9.3 and 9.4).
Local control can emulate the following switch types in Figure 11.5 through Figure 11.7.
Figure 11.5: Local Control Switch Configured as an ON/OFF Switch
Figure 11.6: Local Control Switch Configured as an OFF/MOMENTARY Switch
Figure 11.7: Local Control Switch Configured as an ON/OFF/MOMENTARY Switch
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......