Date Code 20011205
Close Logic
6-1
SEL-311A Instruction Manual
SECTION 6: CLOSE LOGIC
C
LOSE
L
OGIC
This section describes the final logic that controls the close output contact (e.g., OUT103 =
CLOSE). This output contact closes the circuit breaker for other close conditions (e.g., manual
close initiation via serial port or optoisolated inputs).
The close logic in Figure 6.1 provides flexible circuit breaker closing with SEL
OGIC
control
equation settings:
52A (breaker
status)
CL
(close conditions, other than automatic reclosing)
ULCL
(unlatch close conditions, other than circuit breaker status, or close failure)
and setting:
CFD
(Close Failure Time)
See the settings sheet in
Section 9: Setting the Relay
for setting ranges.
Figure 6.1: Close Logic