3-22
Distance and Overcurrent Elements
Date Code 20011205
SEL-311A Instruction Manual
Torque Control Switch Open
If the Torque Control Switch in Figure 3.14 is open, maximum phase current, I
ABC
, cannot get
through to the pickup comparator (setting 51PP) and the curve timing/reset timing functions. For
example, suppose that the Torque Control Switch is closed, I
ABC
is:
I
ABC
> pickup setting 51PP
and the phase time-overcurrent element is timing or is timed out on its curve. If the Torque
Control Switch is then opened, I
ABC
effectively appears as a magnitude of zero (0) to the pickup
comparator:
I
ABC
= 0 A (effective)
<
pickup setting 51PP
resulting in Relay Word bit 51P deasserting to logical 0. I
ABC
also effectively appears as a
magnitude of zero (0) to the curve timing/reset timing functions, resulting in Relay Word bit
51PT also deasserting to logical 0. The phase time-overcurrent element then starts to time to
reset. Relay Word bit 51PR asserts to logical 1 when the phase time-overcurrent element is fully
reset.
Torque Control
Refer to Figure 3.14.
SEL
OGIC
control equation torque control settings (e.g., 51PTC) cannot be set directly to logical 0.
The following are settings examples of SEL
OGIC
control equation torque control setting 51PTC
for phase time-overcurrent element 51PT.
51PTC = 1
Setting 51PTC set directly to logical 1:
The Torque Control Switch closes and phase time-overcurrent element
51PT is enabled and nondirectional.
Note
: All overcurrent element SEL
OGIC
control equation torque control settings
are set directly to logical 1 (e.g., 51PTC = 1) for the factory default
settings. See
SHO Command (Show/View Settings)
in
Section 10: Serial
Port Communications and Commands
for a list of the factory default
settings.
51PTC = IN105 Input IN105 deasserted (51PTC = IN105 = logical 0):
The Torque Control Switch opens and phase time-overcurrent element
51PT is defeated and nonoperational, regardless of any other setting.
Input IN105 asserted (51PTC = IN105 = logical 1):
The Torque Control Switch closes and phase time-overcurrent element
51PT is enabled and nondirectional.
51PTC = M2P
The 51P/51PT uses the Zone 2 mho phase distance element to provide forward
directional control.
Other SEL
OGIC
control equation torque control settings may be set to provide directional control.
See
Overcurrent Directional Control Provided by Torque Control Settings
at the end of
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......