3-24
Distance and Overcurrent Elements
Date Code 20011205
SEL-311A Instruction Manual
Figure 3.15: Residual Ground Time-Overcurrent Element 51GT
Settings Ranges
Table 3.5: Residual Ground Time-Overcurrent Element Settings
Setting Definition
Range
51GP
pickup
OFF, 0.50–16.00 A secondary (5 A nominal phase
current inputs, IA, IB, IC)
OFF, 0.10–3.20 A secondary (1 A nominal phase
current inputs, IA, IB, IC)
51GC
curve type
U1–U5 (US curves) see Figure 9.1–Figure 9.10
C1–C5 (IEC curves)
51GTD
time dial
0.50–15.00 (US curves) see Figure 9.1–Figure 9.10
0.05–1.00 (IEC curves)
51GRS electromechanical
reset timing
Y = Enable electromechanical reset timing
N = 1 cycle reset delay
51GTC SEL
OGIC
control
equation torque
control setting
Relay Word bits referenced in Tables 9.3 and 9.4
or
set directly to logical 1—see note below.
Note
: SEL
OGIC
control equation torque control settings (e.g., 51GTC) cannot be set directly to
logical 0.
See
Section 9: Setting the Relay
for additional time-overcurrent element settings information.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......