Date Code 20011205
Distributed Network Protocol (DNP) 3.00
G-1
SEL-311A Instruction Manual
APPENDIX G: DISTRIBUTED NETWORK PROTOCOL
(DNP) 3.00
O
VERVIEW
The SEL-311A family of relays are available with the option to support Distributed Network
Protocol (DNP) 3.00 L2 Slave protocol. This includes access to metering data, protection
elements (Relay Word), contact I/O, targets, sequential events recorder, breaker monitor, relay
summary event reports, settings groups, and time synchronization. The SEL-311A supports DNP
point remapping.
C
ONFIGURATION
To configure a port for DNP, set the port PROTO setting to DNP. Although DNP may be
selected on any of the available ports, DNP may not be enabled on more than one port at a time.
The following information is required to configure a port for DNP operation:
Label Description
Default
SPEED
Baud rate (300–38400)
2400
DNPADR
DNP Address (0–65534)
0
ECLASS
Class for event data (0–3)
2
TIMERQ
Time-set request interval (0–32767 min.)
0
DECPLA
Currents scaling (0–3 decimal places)
1
DECPLV
Voltages scaling (0–3 decimal places)
1
DECPLM
Miscellaneous data scaling (0–3 decimal places)
1
STIMEO
Select/operate time-out (0–30 sec.)
1.0
DRETRY
Data link retries (0–15)
3
DTIMEO
Data link time-out (0–5 sec.)
1
MINDLY
Minimum time from DCD to Tx (0–1 sec.)
0.05
MAXDLY
Maximum time from DCD to Tx (0–1 sec.)
0.10
PREDLY
Settle time from RTS on to Tx (OFF, 0–30 sec.)
0
PSTDLY
Settle time after Tx to RTS off (0–30 sec.)
0
ANADB
Analog reporting dead band (0–32767 counts)
100
UNSOL
Enable Unsolicited reporting (Y, N)
N
PUNSOL
Enable Unsolicited reporting at power-up (Y, N)
N
REPADR
DNP Address to report to (0–65534)
0
NUMEVE
Number of events to transmit on (1–200)
10
AGEEVE
Age of oldest event to transmit on (0–60 sec.)
2.0
UTIMEO
Unsolicited confirmation timeout (0–50 sec.)
2
The RTS signal may be used to control an external transceiver. The CTS signal is used as a
DCD input, indicating when the medium is in use. Transmissions are only initiated if DCD is de-
asserted. When DCD drops, the next pending outgoing message may be sent once an idle time is
satisfied. This idle time is randomly selected between the minimum and maximum allowed idle
times (i.e., MAXDLY and MINDLY). In addition, the SEL-311A monitors received data and
treats receipt of data as a DCD indication. This allows RTS to be looped back to CTS in cases
where the external transceiver does not support DCD. When the SEL-311A transmits a DNP
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......