background image

ABB Power T&D Company Inc.

Power Automation and Protection Division
Coral Springs, FL 33065

Instruction Leaflet

All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.

Printed in U.S.A

.

I.L. 41-201S

Supersedes I.L. 41-201R, Dated April 1995

Type CV
Voltage Relay

Effective:

January 1997

)

Denotes Change Since Previous Issu

e

!

CAUTION

Before putting relays into service, remove all

blocking which may have been inserted for the

purpose of securing the parts during ship-

ment, make sure that all moving parts operate

freely, inspect the contacts to see that they

are clean and close properly, and operate the

relay to check the settings and electrical con-

nections.

1.

APPLICATION

The Type CV Relays are single-phase induction disc
type relays operating either on under or overvoltage
or both. These relays are applied as a voltage fault
detector operating in conjunction with other protec-

tive relays. The relays are also used as timing
devices for various automatic operations.

2.

CONSTRUCTION AND OPERATION

The types CV-1, CV-2 CV-4, CV-5, CV-6, and CV-7
relays consist of a voltage unit and an indicating con-
tactor switch (ICS). The principal component parts of
the relay and their location are shown in Figures 1, 2,
and 3.

The Type CV-8 relay in addition to the above compo-
nents also has a capacitor which is series tuned with
the main coil of the electromagnet. This tuned circuit
offers a low impedance to fundamental current and a
high impedance to third harmonic currents. Hence,
the relay has a low pickup value for fundamental volt-
age and a much higher value of pickup for third har-
monic voltage. At rated voltage the electromagnet is
saturated causing the circuit to be detuned. The
impedance of the circuit is increased and limits the
fundamental current to a safe value.

2.1.

Voltage Unit (CV)

The overvoltage unit operates on the induction disc
principle. A main tapped coil located on the center
leg of an “E” type laminated structure produces a flux
which divides and returns through the outer legs. A
shading coil causes the flux through the left leg (front
view) to lag the main pole flux. The out-of-phase
fluxes thus produced in the air gap causes a contact
closing torque.

The undervoltage unit operates on the same princi-
ple as the overvoltage unit except the shading coil is
on the right leg (front view). This causes the out-of-
phase fluxes to produce a contact opening torque.

This instruction leaflet applies to the following
types of relay:

CV-1 Long Time Undervoltage Relay

CV-2 Short Time Undervoltage Relay

CV-4 Long Time Overvoltage Relay

CV-5 Short Time Overvoltage Relay

CV-6 Long Time Over or Undervoltage Relay

CV-7 Short Time Over or Undervoltage Relay

CV-8 Low Voltage Pickup Overvoltage Relay

Summary of Contents for CV-1

Page 1: ...cating con tactor switch ICS The principal component parts of the relay and their location are shown in Figures 1 2 and 3 The Type CV 8 relay in addition to the above compo nents also has a capacitor...

Page 2: ......

Page 3: ...e the relay contacts At this value of voltage the moving contacts will leave the backstop of the dial and move to close the front contacts Normal operation of the two relays is such that the CV 1 and...

Page 4: ...relay with a 67 volt continuous and a 16 to 40 volt relay with a con tinuous of 199 volts is also available However the operate times of the adjustable CV 8 relay will differ from Figure 10a and will...

Page 5: ...ted out Timing tests should be conducted after the resistor is used to change the pickup This will insure proper coordination time for the desired pickup setting Figure 10b applies when the resistor i...

Page 6: ...11 Case Figure 7 Internal Schematic Of The Type CV 8 67 Volt Relay In Type FT 21 Case Figure 8 Internal Schematic Of The Type CV 8 199 Volt Relay In Type FT 21 Case With Adjustable Pickup Figure 9 Int...

Page 7: ...r double trip relay the follow on the stationary contacts should be approximately 1 64 b For relays identified with a T located at lower left of stationary contact block the index mark on the movement...

Page 8: ...of the danger of embedding small particles in the face of the soft silver contact and thus impair ing the contact 8 CALIBRATION Use the following procedure for calibrating the relay if the relay has...

Page 9: ...able 1 b CV 4 and CV 5 Overvoltage Relay CV 8 Low Pickup Overvoltage Relay Apply the indicated voltage of Table 1 and mea sure the operating time Adjust the permanent magnet keeper until the operating...

Page 10: ...I L 41 201S 10 Figure 10a Typical Time Curves Of The Type CV 8 Low Pickup Overvoltage Relay Curve 619537...

Page 11: ...I L 41 201S 11 Figure 10b Typical Time Curves For Type CV 8 Overvoltage Relay With Resistor Set For Maximum Pickup Curve 619541...

Page 12: ...Time Undervoltage Relay Curve 418251 TIME DIAL SETTING 11 10 9 8 7 6 5 4 3 2 1 1 2 TYPICAL TIME CURVES TYPE CV 1 UNDERVOLTAGE RELAY 50 60 HERTZ PERCENT TAP VALUE VOLTAGE 0 10 20 30 40 50 60 70 80 90 1...

Page 13: ...V 2 Short Time Undervoltage Relay Curve 418250 TYPICAL TIME CURVES TYPE CV 2 UNDERVOLTAGE RELAY 50 60 HERTZ TIME DIAL SETTING 1 2 1 2 3 4 5 6 7 8 9 10 11 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0...

Page 14: ...I L 41 201S 14 Figure 13 Typical Time Curves Of The Type CV 4 Long Time Overvoltage Relay Curve 406C881 PERCENT OF TAP VALUE VOLTAGE...

Page 15: ...I L 41 201S 15 Figure 14 Typical Time Curves Of The Type CV 5 Long Time Overvoltage Relay Curve 406C884...

Page 16: ...I L 41 201S 16 Figure 15 Typical Time Curves Of The Type CV 6 Long Time Over And Undervoltage Relay Curve 406C882...

Page 17: ...I L 41 201S 17 Figure 16 Typical Time Curves Of The Type CV 7 Short Time Over And Undervoltage Relay Curve 406C883...

Page 18: ...I L 41 201S 18 Figure 17 Typical Sensitivity vs Frequency Curve For Type CV 8 Low Pickup Overvoltage Relay Curve 418270 Sub 2...

Page 19: ...I L 41 201S 19 Figure 18 Diagram Of Test Connections Of The Type CV Undervoltage Relay Figure 19 Diagram Of Test Connections Of The Type CV Overvoltage Relay 183A024 Sub 2 183A023 Sub 2...

Page 20: ...A ABB Power T D Company Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 954 752 6700 FAX 305 345 5329 Figure 20 Outline And Drilling For FT 11 Case Used For Projection And or Semi flush Case 5...

Reviews: