Date Code 20011205
Close Logic
6-3
SEL-311A Instruction Manual
Set Close
SEL
OGIC
control equation setting CL is the only logic input that can set the CLOSE Relay Word
bit. In SEL
OGIC
control equation setting CL = CC, Relay Word bit CC asserts for execution of
the CLOSE Command. See
CLO Command (Close Breaker)
in
Section 10: Serial Port
Communications and Commands
for more information on the CLOSE Command.
Unlatch Close
SEL
OGIC
control equation setting ULCL is usually set with the TRIP Relay Word bit. This
prevents the CLOSE Relay Word bit from being asserted any time the TRIP Relay Word bit is
asserted (TRIP takes priority). See
Trip Logic
in
Section 5: Trip and Target Logic
.
SEL
OGIC
control equation setting 52A is set with optoisolated input IN101. Input IN101 is
connected to a 52a circuit breaker auxiliary contact. When a closed circuit breaker condition is
detected, the CLOSE Relay Word bit is deasserted to logical 0. Setting 52A can handle a 52a or
52b circuit breaker auxiliary contact connected to an optoisolated input (see
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more 52A setting
examples).
With setting CFD = 60.00 cycles, once the CLOSE Relay Word bit asserts, it remains asserted at
logical 1 no longer than a maximum of 60 cycles. If the Close Failure Timer times out, Relay
Word bit CF asserts to logical 1, forcing the CLOSE Relay Word bit to logical 0.
Defeat the Close Logic
If SEL
OGIC
control equation circuit breaker auxiliary setting 52A is set with numeral 0
(52A = 0), then the close logic is inoperable.
Circuit Breaker Status
Refer to the bottom of Figure 6.1. Note that SEL
OGIC
control equation setting 52A (circuit
breaker status) is available as Relay Word bit 52A. This makes it convenient to set other
SEL
OGIC
control equations. For example, if the following setting is made:
52A = IN101
(52a auxiliary contact wired to input IN101)
or
52A = !IN101
(52b auxiliary contact wired to input IN101)
then if breaker status is used in other SEL
OGIC
control equations, it can be entered as 52A - the
user doesn’t have to enter IN101 (for a 52a) or !IN101 (for a 52b). For example, refer to
Rotating Default Display
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
. If
circuit breaker status indication is controlled by display point setting DP2:
DP2 = IN101
This can be entered instead as:
DP2 = 52A
(presuming SEL
OGIC
control equation setting 52A = IN101 is made).
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......