12-2
Standard Event Reports and SER
Date Code 20011205
SEL-311A Instruction Manual
·
TRI
(Trigger Event Reports) serial port command executed
·
Output contacts OUT101 through OUT107 pulsed via the serial port or front-panel
PUL
(Pulse Output Contact) command
Relay Word Bit TRIP
Refer to Figure 5.1. If Relay Word bit TRIP asserts to logical 1, an event report is automatically
generated. Any trip condition that asserts in setting TR causes the TRIP Relay Word bit to assert
immediately. The Relay Word bit TRIP asserts, and an event report is automatically generated.
Any condition that causes a trip does not have to be entered in SEL
OGIC
control equation setting
ER.
Relay Word bit TRIP (in Figure 5.1) is usually assigned to an output contact for tripping a circuit
breaker (e.g., SEL
OGIC
control equation setting OUT101 = TRIP).
Programmable SEL
OGIC
Control Equation Setting ER
The programmable SEL
OGIC
control equation event report trigger setting ER is set to trigger
standard event reports for conditions other than trip conditions. When setting ER sees a logical 0
to logical 1 transition, it generates an event report (if the SEL-311A Relay is not already
generating a report that encompasses the new transition). The factory setting is:
ER = /M2P + /Z2G + /51G + /50P1 + /LOP
The elements in this example setting are:
M2P Zone 2 phase-distance element asserted (see Figure 3.5).
Z2G
Zone 2 ground-distance element asserted (see Figure 3.7).
51G
Residual ground current above pickup setting 51GP for residual ground
time-overcurrent element 51GT (see Figure 3.15).
50P1 Phase current above pickup setting 50P1P for phase overcurrent element
50P1 (see Figure 3.10).
LOP
Loss of potential (LOP) asserts (see Figure 4.1).
Note the rising edge operator/in front of each of these elements. See
Appendix F: Setting
SEL
OGIC
Control Equations
for more information on rising edge operators and SEL
OGIC
control equations in general.
Rising edge operators are especially useful in generating an event report at fault inception and
then generating another later if for example a breaker failure condition occurs. If at the inception
of a ground fault, pickup indicator 51G asserts and an event report is generated:
ER = ... + /51G + ... = logical 1 (for one processing interval)
Even though the 51G pickup indicator will remain asserted for the duration of the ground fault,
the rising edge operator/in front of 51G (/51G) causes setting ER to be asserted for only one
processing interval. Other operators in the setting ER SEL
OGIC
control equation can trigger
event reports while 51G is still asserted.
Falling edge operators \ are also used to generate event reports. See Figure F.2 in
Appendix F:
Setting SEL
OGIC
Control Equations
for more information on falling edge operators.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......