2-12
Installation
Date Code 20011205
SEL-311A Instruction Manual
Output Contact Jumpers
Jumpers JMP21–JMP29 (but not JMP23) correspond to contact outputs ALARM through
OUT101. Figure 2.7 shows the exact location and correspondence. With a jumper in the A
position, the corresponding output contact is an “a” type output contact. An “a” type output
contact is open when the associated SEL
OGIC
equation is deasserted, and closed when the
associated SEL
OGIC
equation is asserted. With a jumper in the B position, the corresponding
output contact is a “b” type output contact. A “b” type output contact is closed when the
associated SEL
OGIC
equation is deasserted, and open when the associated SEL
OGIC
equation is
asserted. These jumpers are soldered in place.
In Figure 2.7, note that the ALARM output contact is a “b” type output contact and the other
output contacts are all “a” type output contacts. This is how these jumpers are configured in a
standard relay shipment. Refer to Figure 7.26 for examples of output contact operation for
different output contact types.
“Extra Alarm” Output Contact Control Jumper
All the SEL
-
311A Relays have dedicated alarm output contacts (labeled ALARM—see Figure
2.2 and Figure 2.3). Often more than one alarm output contact is needed for such applications as
local or remote annunciation, backup schemes, etc.
Convert the output contact adjacent to the dedicated ALARM output contact to operate as an
“extra alarm” output contact by moving jumper JMP23 on the main board (see Table 2.2).
With the jumper in one position, the output contact operates regularly. With the jumper in the
other position, the output contact is driven by the same signal that operates the dedicated
ALARM output contact (see Table 2.2).
Table 2.2: Move Jumper JMP23 to Select Extra Alarm
Position
Output Contact OUT107 Operation
Output contact OUT107 is operated by Relay Word bit OUT107.
Jumper JMP23 comes in this position in a standard relay shipment (see
Figure 7.26).
“Extra Alarm” output contact is operated by alarm logic/circuitry.
Relay Word bit OUT107 does not have any effect on output contact
OUT107 when jumper JMP23 is in this position (see Figure 7.26).
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......