Date Code 20011205
Firmware Upgrade Instructions
B-5
SEL-311A Instruction Manual
14. Issue the Version (
VER
) command and check the part number from the label on the
firmware diskette against the part number on the screen. If they match, go to Step 15;
otherwise, type
PAR <ENTER>
and type the number from the diskette label and press
<ENTER>
. If the relay reinitializes after saving the changes, go to Access Level 2.
15. Execute the Status (
STA
) command to verify that all relay self-test parameters are
within tolerance, and that the relay is enabled.
16. Apply current and voltage signals to the relay. Issue the
MET
command; verify that the
current and voltage signals are correct. Issue the Trigger (
TRI
) and Event (
EVE
)
commands. Verify that the current and voltage signals are correct in the event report.
The relay is now ready for your commissioning procedure.