D-10
Configuration, Fast Meter, and Fast Operate Commands
Date Code 20011205
SEL-311A Instruction Manual
A5E3 Fast Operate Breaker Control
The external device sends the following message to perform a fast breaker open/close:
Data Description
A5E3 Command
06 Length
1 byte
Operate code:
31–OPEN
breaker
11–CLOSE
breaker
1 byte
Operate Validation: 4 • Operate code + 1
checksum
1-byte checksum of preceding bytes
The relay performs the specified breaker operation if the following conditions are true:
1. Conditions 1–5 defined in the A5E0 message are true.
2. The breaker jumper (JMP2B) is in place on the SEL-311A Relay main board.
A5CD Fast Operate Reset Definition Block
In response to an A5CD request, the relay sends the configuration block for the Fast Operate
Reset message:
Data Description
A5CD Command
0E Message
length
01
The number of Fast Operate reset codes supported
00
Reserved for future use
Per Fast Operate reset code, repeat:
00
Fast Operate reset code (e.g., “00” for target reset)
54415220520000
Fast Operate reset description string (e.g., “TAR R”)
xx Checksum
A5ED Fast Operate Reset Command
The Fast Operate Reset commands take the following form:
Data Description
A5ED Command
06
Message Length—always 6
00
Operate Code (e.g., “00” for target reset, “TAR R”)
01
Operate Validation - (4 + Operate Code) + 1
xx Checksum
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......