7-34
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311A Instruction Manual
To verify ALARM output contact mechanical integrity, execute the serial port command
PULSE
ALARM
. Execution of this command momentarily deenergizes the ALARM output contact
coil.
The Relay Word bit ALARM is deasserted to logical 0 when the relay is operational. When the
serial port command
PULSE ALARM
is executed, the ALARM Relay Word bit momentarily
asserts to logical 1. Also, when the relay enters Access Level 2, the ALARM Relay Word bit
momentarily asserts to logical 1 (and the ALARM output contact coil is deenergized
momentarily).
Notice in Figure 7.26 that all possible combinations of ALARM output contact coil states
(energized or deenergized) and output contact types (a or b) are demonstrated. See
Output
Contact Jumpers
in
Section 2: Installation
for output contact type options.
Table 2.2
Table 2.3
Figure 7.26: Logic Flow for Example Output Contact Operation
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......