5-4
Trip and Target Logic
Date Code 20011205
SEL-311A Instruction Manual
The front-panel TARGET RESET button or the
TAR R
(Target Reset) serial port command is
primarily used during testing. Use these to force the TRIP Relay Word bit to logical 0 if test
conditions are such that setting ULTR does not assert to logical 1 to automatically deassert the
TRIP Relay Word bit instead.
Other Applications for the Target Reset Function
Note that the combination of the TARGET RESET pushbutton and the
TAR R
(Target Reset)
serial port command is also available as Relay Word bit TRGTR. See Figure 5.4 and
accompanying text for applications for Relay Word bit TRGTR.
Factory Settings Example (Using Setting TR)
In this example the “switch-onto-fault” trip logic at the top of Figure 5.1 is not used. The
SEL
OGIC
control equation trip setting TR is now the only input into OR-1 gate and flows into the
“seal-in and unlatch” logic for Relay Word bit TRIP.
The factory settings for the trip logic SEL
OGIC
control equation settings are:
TR = M1P + Z1G + M2PT + Z2GT + 51GT + OC
(trip conditions)
ULTR = !(50L + 51G)
(unlatch trip conditions)
The factory setting for the Minimum Trip Duration Timer setting is:
TDURD = 9.000 cycles
See the settings sheets in
Section 9: Setting the Relay
for setting ranges.
Set Trip
In SEL
OGIC
control equation setting TR = M1P + Z1G + M2PT + Z2GT + 51GT + OC:
·
Distance elements M1P, M2PT, Z1G, and Z2GT and time-overcurrent element 51GT
trip directly. Time-overcurrent and definite-time overcurrent elements can be torque
controlled (e.g., element 51GT is torque controlled by SEL
OGIC
control equation setting
51GTC). Check torque control settings to see if any control is applied to time-
overcurrent and definite-time overcurrent elements. Such control is not apparent by
mere inspection of trip setting TR or any other SEL
OGIC
control equation trip setting.
·
Relay Word bit OC asserts for execution of the OPEN Command. See
OPE Command
(Open Breaker)
in
Section 10: Serial Port Communications and Commands
for more
information on the OPEN Command.
With setting TDURD = 9.000 cycles, once the TRIP Relay Word bit asserts via SEL
OGIC
control
equation setting TR, it remains asserted at logical 1 for a minimum of 9 cycles.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......