Quick Guide UFR1001E 

 

updated: 2019-04-24/Ba 

from Firmware: 0-10

 

 

UFR1001E 

12420-0751-13 

Seite

 

1 / 8 

www.ziehl.de 

- NA-protection according to VDE-AR-N 4105:2011+2018-11, power generators at the low 
voltage grid, TAR medium voltage VDE-AR-N 4110:2018-11

 

- for use in power generators at the medium voltage grid according to BDEW 
- with selectable vector shift detection and Rate of Change of Frequency (ROCOF,df/dt) 

 
Detailed operating manual see:

 

https://www.ziehl.com/en/products/?view=detail&detail=54

 

New, Firmware 0-10:   default setting program 2 for low voltage VDE-AR-N 4105:2018-11 
4 new programs (11-14) for medium voltage according to 4110:2018-11, new test mode

 

(display of the firmware function  

8

Info

8

 

 

8

fnr 

 

or press “Set” for >10 s)

 

 

General Notes 

Compliance  with  the  following  instructions  is  mandatory  to  ensure  the  functionality  and  safety  of  the 
product.  If the following  instructions  given  especially  but  not  limited for  general  safety,  transport, storage, 
mounting,  operating  conditions,  start-up  and  disposal  /  recycling  are  not  observed,  the  product  may  not 
operate safely and may cause a hazard to the life and limb of users and third parties.  
Deviations  from  the  following  requirements  may  therefore  lead  both  to  the  loss  of  the  statutory  material 
defect  liability  rights  and  to  the  liability  of  the  buyer  for  the  product  that  has  become  unsafe  due  to  the 
deviation from the specifications. 

 

Operating controls 

 
 
 

 
 
 
 
 
 
 

Test button 

  

Press 
shortly 

Display 

test-menu:

 Relay K1 (

8

tst1

8

) or K2 (

8

tst2

8

) can be tested independently. (3min 

without a button is pressed = go back to the normal mode) 

LEDs Frequency / voltage, above / below threshold 

(red)

 

 

ON, 

8

AL  

8

or 

8

AL M

  

Above / below threshold 

 

Flashing, 

8

AL 

88

or 

8

AL M

  

OFF-delay 

8

dof 

8

 active 

LED Vektor shift 

(VSR, red)

 

 

ON, 

8

AL  

8

 

Threshold value for vector shift exceeded 

 

Flashing, 

8

AL 

8

 

OFF-delay 

8

dof 

8

 active 

LEDs  Relay status 

(yellow)

 

 

OFF 

Relays de-energized 

ON 

Relays energized 

Digital display 4-digit 

(red)

 

 

Depending on program, display of current voltage, frequency, vector shift, average value 

 

Display of alarm message 

8

AL  

8

8

aL M

8

 

Display of error with error code e.g.  

8

Err9

8

 

LED Time 

(yellow)

 

 

ON 

A time is displayed 

Backmost decimal point 

(red)

 

  

OFF 

Display mode 

  

Lightning 

Menu mode 

 

Flashing 

Configuration mode 

Summary of Contents for UFR1001E

Page 1: ...given especially but not limited for general safety transport storage mounting operating conditions start up and disposal recycling are not observed the product may not operate safely and may cause a...

Page 2: ...r11 Pr12 Pr13 Pr14 U 59 S2 59 S2 u Alarm on off on Pr11 Pr12 Pr13 Pr14 u Overvoltage V 287 on on on on H Hysteresis V 35 0 69 2 120 287 498 dal Response time s 0 10 1 0 1 0 3 0 3 0 dof OFF delay s 60...

Page 3: ...f off off off off off uonf voltage V 46 0 46 0 46 0 20 0 20 0 46 0 46 0 Vsr 78 vsr Alarm on off stby Stby stby stby stby stby stby vsr Vector shift 10 0 10 0 10 0 10 0 10 0 10 0 10 0 dof OFF delay s 3...

Page 4: ...luation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default setting e g through ripple control receiv...

Page 5: ...igital output Error in Program 3 6 additionally the 2nd threshold value L1 L2 L3 N Phase L1 L2 L3 and neutral conductor Important notice In the supply line in the vicinity of the device easily accessi...

Page 6: ...oltage 2x under voltage 2x over frequency 2x under frequency 10min average value 1x vector shift 1x ROCOF 230V G98 G83 2 G99 G59 3 21 3 AC without N 400V 22 3 AC with N 63 5V 23 3 AC without N 110V de...

Page 7: ...tion Country Standard 2 3 AC N VDE AR N 4105 2018 11 3 AC N VDE AR N 4110 2018 12 3 AC 13 3 2 1 AC N 14 3 AC 3 3 AC N BDEW Juni 2008 nach 3 2 3 3 1 4 3 AC 5 3 2 1 AC N 6 3 AC 20 3 2 1 AC N G98 G83 2 G...

Page 8: ...hreshold values 8Err98 appears in the display Configuration error Reset to factory settings see Program setup A time expires in the display If a OFF delay 8dof 8 is active the time runs down in the di...

Reviews: