background image

 

UFR1001E  

12420-0751-13

  

Page

 

8 / 8 

www.ziehl.de 

  

 

Troubleshooting 

Error 

Cause 

Remedy 

8

EEEE

8

 

or

 

8

-EEE

8

 appears 

in the display 

Measured voltage, frequency 
or the vector shift is too large 
or too small 

Consider the measuring range 

8

Err4

8

  

appears in the display

 

Tolerance error, internal 
measurement value deviation 
of both channels 

Perform a reset 

  

interrupt the control supply voltage  

for >5 s 

*

 

8

Err5

8

  

appears in the display

 

Error internal regulation 

8

Err6

8

  

appears in the display

 

Communication error internal 
interface 

8

Err7

8

 

appears in the 

display even after 2 
automatic repeated trials of 
switching on + LED K1

 

and/or K2 is lightning

 

Error feedback contacts, 
switches not connected 
correctly or broken or  
switches are controlled from 
other device 

Feedback contacts not connected 
- set 

8

rel .

8

 

 

8

trel.

8

 

 

8

 off

8

 

Feedback contacts connected 
- check the correct connection 
- Adjust the turn-on time under  

8

rel .

8

 

 

8

trel.

8

 greater then the switch-on 

time of the switcher 
- Perform a reset 

 press Set/Reset  

for >2 s 

8

Err8

8

  

appears in the display

 

Hysteresis error: 
overlapping of the release 
points 

Upper threshold value must be higher 
than the lower threshold value, check the 
threshold values 

8

Err9

8

  

appears in the display

 

Configuration error 

Reset to factory settings, see “Program 
setup” * 

A time expires in the display

 

If a OFF-delay 

8

dof

 

8

 is 

active, the time runs down in 
the display (the shortest one 
first) 

Wait until the time is complete 
(depending on the setting, several times 
may elapse one after the other) 

Device cannot be configured 
/ only the threshold values 
can be configured 

Code lock / Sealing activated 

When having problems with the code 
lock (Pin forgotten), the lock can be 
deactivated and the pin can be reset to 

504 , by pressing the button   until  

8

Code

8

 

/  off

8

 is shown in the display, 

while switching on the control supply 
voltage 

 

Implausible voltage values 

Pr selected with N, but N not 
connected 

Select Pr without N or connect N 

8

Loc 

8

  

appears in the display

 

Sealing is active 

See „Program setup“ 

8

Code

8

  

appears in the display

 

Code lock is active 

See „Code lock“ 

8

stby

8

 

appears in the 

display

 

Standbymode, E1-E2 closed 

check parameter 

8

 vsr.

8

  

8

Al  

8

 

and LED Q3 (f>) is 

on, reading value in good 
range

 

hysteresis for

 

8

F, 

8

 

incorrectly 

Ceck hysteresis for reset point 
50,05 Hz 

8

noY1

8

 

or 

8

noY2

8

 appears 

in the display

 

Feedback contact not 
connected or switch does not 
switch 

Check the connection and function of the 
switch. 
Its normal in Pr2 at Test 2 

8

noY2

8

 
*

 If the error cannot be patched by a reset, send back to factory for repair.

 

 
 

Summary of Contents for UFR1001E

Page 1: ...given especially but not limited for general safety transport storage mounting operating conditions start up and disposal recycling are not observed the product may not operate safely and may cause a...

Page 2: ...r11 Pr12 Pr13 Pr14 U 59 S2 59 S2 u Alarm on off on Pr11 Pr12 Pr13 Pr14 u Overvoltage V 287 on on on on H Hysteresis V 35 0 69 2 120 287 498 dal Response time s 0 10 1 0 1 0 3 0 3 0 dof OFF delay s 60...

Page 3: ...f off off off off off uonf voltage V 46 0 46 0 46 0 20 0 20 0 46 0 46 0 Vsr 78 vsr Alarm on off stby Stby stby stby stby stby stby vsr Vector shift 10 0 10 0 10 0 10 0 10 0 10 0 10 0 dof OFF delay s 3...

Page 4: ...luation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default setting e g through ripple control receiv...

Page 5: ...igital output Error in Program 3 6 additionally the 2nd threshold value L1 L2 L3 N Phase L1 L2 L3 and neutral conductor Important notice In the supply line in the vicinity of the device easily accessi...

Page 6: ...oltage 2x under voltage 2x over frequency 2x under frequency 10min average value 1x vector shift 1x ROCOF 230V G98 G83 2 G99 G59 3 21 3 AC without N 400V 22 3 AC with N 63 5V 23 3 AC without N 110V de...

Page 7: ...tion Country Standard 2 3 AC N VDE AR N 4105 2018 11 3 AC N VDE AR N 4110 2018 12 3 AC 13 3 2 1 AC N 14 3 AC 3 3 AC N BDEW Juni 2008 nach 3 2 3 3 1 4 3 AC 5 3 2 1 AC N 6 3 AC 20 3 2 1 AC N G98 G83 2 G...

Page 8: ...hreshold values 8Err98 appears in the display Configuration error Reset to factory settings see Program setup A time expires in the display If a OFF delay 8dof 8 is active the time runs down in the di...