UFR1001E
12420-0751-13
Page
6 / 8
www.ziehl.de
Program setup
The suitable program must be set on the UFR1001E in accordance with the application. If the
UFR1001E is sealed/locked (red LED
lightning), sealing has to be deactivated first.
Pr
Connection
Limit
Voltage
Country / Standard
* 2
3 AC with N
Niederspannung
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
,1x
vector shift
1x ROCOF
230V
VDE-AR-N 4105:2018
1
3 AC with N
Niederspannung
1x
over voltage
, 1x
under voltage
1x
over frequency
, 1x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
230V
VDE-AR-N 4105:2011
7
2/1 AC with N
11(3) 3 AC with N
Mittelspannung
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
63,5V
VDE-AR-N 4110:2018
(BDEW Juni 2008 by
3.2.3.3-1)
12(4) 3 AC without N
100V
13(5) 3/2/1 AC with N
230V
14(6) 3 AC without N
400V
10
3/2/1 AC with N
1x
over voltage
, 1x
under voltage
1x
over frequency
, 1x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
230V
ÖVE/ÖNORM
E 8001-4-712
15
3 AC with N
230V
VSE/EEA-CH 2014
20
3/2/1 AC with N
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
230V
G98(G83/2) +
G99(G59/3)
21
3 AC without N
400V
22
3 AC with N
63,5V
23
3 AC without N
110V
* default setting,
default settings
8
pr 3
8
...
8
Pr 6
8
,
8
pr10
8
,
8
pr15
8
,
8
pr20
8
...
8
Pr23
8
see
https://www.ziehl.com/en/products/?view=detail&detail=54
Adjustment process:
•
If present, remove seal (only authorised person)
•
Apply control supply voltage at A1-A2
•
Slightly lift the button cover and turn 180°
•
Actuate the small blue button by strong pressing on the button cover (LED starts flashing) until the
green LED
is lightning.
•
Press button
1x
→
Display
8
Info.
8
•
Press button 5x
→
Display
8
Pr 1.
8
•
Set the program with the buttons
•
Press button 1x
→
Display
8
no.
8
•
Press button
1x
→
Display
8
yes.
8
•
Press button
Device resets and starts with the newly selected program
Hint:
When changing programs, all parameters of the selected program are reset to “default settings“ (
see
table „Default settings“
). Only change the parameters after having selected the correct program.
Technical data
Rated control supply voltage U
s
:
24-270V AC/DC -
15…+10 %, DC / 40-70 Hz, <5 VA
Output relays:
2 c/o contacts
Max. switching voltage
400 V AC
Inrush current (at 10 % ED)
25 A max. 4 s / 50 A max. 1 s
Rated operational current I
e
(AC15)
230 V AC / 6 A
Fuse rating to achieve short-ciruit protection
max. gG/gL/B 6 A