UFR1001E  

12420-0751-13

  

Page

 

6 / 8 

www.ziehl.de 

  

 

Program setup 

The suitable program must be set on the UFR1001E in accordance with the application. If the  
UFR1001E is sealed/locked (red LED 

lightning), sealing has to be deactivated first. 

 

Pr 

Connection 

Limit 

Voltage 

Country / Standard 

* 2 

3 AC with N 

Niederspannung 
2x 

over voltage

,          2x 

under voltage

 

2x 

over frequency

,     2x 

under frequency

 

10min 

average value

,1x 

vector shift

 

1x ROCOF 

230V 

 

 

VDE-AR-N 4105:2018 

3 AC with N 

Niederspannung 
1x 

over voltage

,          1x 

under voltage

 

1x 

over frequency

,     1x 

under frequency

 

10min 

average value

, 1x 

vector shift

 

1x ROCOF 

230V 

 

 

VDE-AR-N 4105:2011 

2/1 AC with N 

11(3)  3 AC with N 

Mittelspannung 
2x 

over voltage

,          2x 

under voltage

 

2x 

over frequency

,     2x 

under frequency

 

10min 

average value

, 1x 

vector shift

 

1x ROCOF 

63,5V 

 

VDE-AR-N 4110:2018 

(BDEW Juni 2008 by 

3.2.3.3-1) 

12(4)  3 AC without N 

100V 

13(5)  3/2/1 AC with N 

230V 

14(6)  3 AC without N 

400V 

10 

3/2/1 AC with N 

1x 

over voltage

,          1x 

under voltage

 

1x 

over frequency

,     1x 

under frequency

 

10min 

average value

, 1x 

vector shift

 

1x ROCOF 

230V 

 

ÖVE/ÖNORM 

E 8001-4-712 

15 

3 AC with N 

230V 

 

VSE/EEA-CH 2014 

20 

3/2/1 AC with N 

2x 

over voltage

,          2x 

under voltage

 

2x 

over frequency

,     2x 

under frequency

 

10min 

average value

, 1x 

vector shift

 

1x ROCOF 

230V 

 

G98(G83/2) + 

G99(G59/3) 

21 

3 AC without N 

400V 

22 

3 AC with N 

63,5V 

23 

3 AC without N 

110V 

* default setting,

 

default settings

 

8

pr 3

8

 ... 

8

Pr 6

8

8

pr10

8

8

pr15

8

8

pr20

8

 ... 

8

Pr23

8

 

see 

https://www.ziehl.com/en/products/?view=detail&detail=54 

Adjustment process: 

  If present, remove seal (only authorised person) 

  Apply control supply voltage at A1-A2 

  Slightly lift the button cover and turn 180° 

  Actuate the small blue button by strong pressing on the button cover (LED starts flashing) until the 

green LED 

 is lightning. 

  Press button 

 1x 

 Display 

8

Info.

8

 

  

  Press button   5x 

 Display 

8

Pr 1.

8

 

  Set the program with the buttons 

 

 

  Press button   1x 

 Display 

8

  no.

8

 

  

  Press button 

 1x 

 Display 

8

 yes.

8

 

  

  Press button   

 

  Device resets and starts with the newly selected program

 

  

Hint: 

When changing programs, all parameters of the selected program are reset to “default settings“ (

see 

table „Default settings“

). Only change the parameters after having selected the correct program. 

 

 

Technical data 

Rated control supply voltage U

s

24-270V AC/DC -

15…+10 %, DC / 40-70 Hz, <5 VA 

Output relays: 

2  c/o contacts   

 

Max. switching voltage  

 

400 V AC 

 

Inrush current (at 10 % ED) 

 

25 A max. 4 s / 50 A max. 1 s 

 

Rated operational current I

e

 (AC15) 

 

230 V AC / 6 A 

 

Fuse rating to achieve short-ciruit protection 

 

max. gG/gL/B 6 A 

Summary of Contents for UFR1001E

Page 1: ...given especially but not limited for general safety transport storage mounting operating conditions start up and disposal recycling are not observed the product may not operate safely and may cause a...

Page 2: ...r11 Pr12 Pr13 Pr14 U 59 S2 59 S2 u Alarm on off on Pr11 Pr12 Pr13 Pr14 u Overvoltage V 287 on on on on H Hysteresis V 35 0 69 2 120 287 498 dal Response time s 0 10 1 0 1 0 3 0 3 0 dof OFF delay s 60...

Page 3: ...f off off off off off uonf voltage V 46 0 46 0 46 0 20 0 20 0 46 0 46 0 Vsr 78 vsr Alarm on off stby Stby stby stby stby stby stby vsr Vector shift 10 0 10 0 10 0 10 0 10 0 10 0 10 0 dof OFF delay s 3...

Page 4: ...luation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default setting e g through ripple control receiv...

Page 5: ...igital output Error in Program 3 6 additionally the 2nd threshold value L1 L2 L3 N Phase L1 L2 L3 and neutral conductor Important notice In the supply line in the vicinity of the device easily accessi...

Page 6: ...oltage 2x under voltage 2x over frequency 2x under frequency 10min average value 1x vector shift 1x ROCOF 230V G98 G83 2 G99 G59 3 21 3 AC without N 400V 22 3 AC with N 63 5V 23 3 AC without N 110V de...

Page 7: ...tion Country Standard 2 3 AC N VDE AR N 4105 2018 11 3 AC N VDE AR N 4110 2018 12 3 AC 13 3 2 1 AC N 14 3 AC 3 3 AC N BDEW Juni 2008 nach 3 2 3 3 1 4 3 AC 5 3 2 1 AC N 6 3 AC 20 3 2 1 AC N G98 G83 2 G...

Page 8: ...hreshold values 8Err98 appears in the display Configuration error Reset to factory settings see Program setup A time expires in the display If a OFF delay 8dof 8 is active the time runs down in the di...

Reviews: