P746/EN CM/F21
Commissioning and Maintenance
(CM) 10-24
MiCOM P746
CM
To test the Phase comparison pick-up only:
When an unlatched Led or a unlatched output relay is mapped on a PhComp Blk Zx or
PhComp Blk Zx Y ddb, the 2 following tests can be performed.
Note:
PhCompBlk Zx ddb is an AND gate of the PhComp Blk Zx A, B, C
ddbs so it will only change for three phase test.
One showing no operation at m = 99% of x% and one showing operation at n = 101% of x%.
First test:
•
Inject outgoing I
1
= m% of CT1 and ingoing I
2
.= I
1
for 10s (for example).
•
No Led or relay output pick-up
Second test:
•
Inject outgoing I
1
= n% of CT1 and ingoing I
2
.= I
1
for 10s (for example).
•
Led or relay output pick-up
Note:
The same test can be performed to test it on the CZ using the
adequate ddbs.
6.2.1.2
Slopes and thresholds
If a LED has been assigned to display the trip information, these may be used to indicate
correct operation. If not, monitor option will need to be used – see the next paragraph.
On P746 go to GROUP1-->BUSBAR PROTECT and set I
D
>1 Alarm timer to 100s
Then go to COMMISSION TESTS column in the menu, scroll down and change cells
[Monitor Bit 1] to [BUSBAR_TRIPPING]. Doing so, cell [Test Port Status] will appropriately
set or reset the bits that now represent BUSBAR_TRIPPING (with the rightmost bit
representing Busbar Trip. From now on you should monitor the indication of [Test Port
Status]. Make a note of which elements need to be re-enabled or re-set after testing.
Test of I
D
>2:
I
D
>1 Alarm Timer should be set to 100s during testing.
Inject a I
2
current smaller than I
D
>2 and slowly increase I
2
until tripping.
Test of the operating time of the differential element:
Inject a I
2
current greater than twice I
D
>2 threshold and measure the operating time of the
differential element.
Test of I
D
>1:
I
D
>1 Alarm Timer should be set to 100ms.
Inject a I
2
current smaller than I
D
>1 and slowly increase I
2
until circuit fault appears (LED
Alarm of LED circuitry fault).
Test of I
D
>1 Alarm Timer:
I
D
>1 Alarm Timer should be set to 5s.
Inject a I2 current greater than twice the I
D
>1 threshold and check that the Circuitry Fault
Alarm is coming in 5s.
Summary of Contents for MiCOM P746
Page 4: ......
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 16: ...P746 EN IT G31 Introduction MiCOM P746...
Page 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Page 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Page 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Page 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Page 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Page 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Page 114: ...P746 EN OP G31 Operation MiCOM P746...
Page 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Page 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Page 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Page 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Page 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Page 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Page 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Page 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Page 280: ......
Page 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Page 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Page 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Page 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Page 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Page 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Page 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Page 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Page 438: ......
Page 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Page 468: ......
Page 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Page 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Page 502: ......
Page 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Page 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Page 529: ......