P746/EN AP/G31
Application Notes
(AP) 6-
18
MiCOM
P746
4.3
Trip relays and Trip Circuit Supervision
Any relays contact can be used for tripping signals from busbar protection, overcurrent
protection and breaker failure.
The trip circuit, in most protective schemes, extends beyond the relay enclosure and passes
through components such as fuses, links, relay contacts, auxiliary switches and other
terminal boards. This complex arrangement, coupled with the importance of the trip circuit,
has led to dedicated schemes for its supervision.
Several trip circuit supervision schemes with various features can be produced with the
P746. Although there are no dedicated settings for TCS, in the following schemes can be
produced using the programmable scheme logic (PSL). A user alarm is used in the PSL to
issue an alarm message on the relay front display. If necessary, the user alarm can be re-
named using the menu text editor to indicate that there is a fault with the trip circuit.
4.3.1 TCS
scheme
1
4.3.1.1 Scheme
description
P2228ENa
Optional
AP
FIGURE 2: TCS SCHEME 1
This scheme provides supervision of the trip coil with the breaker open or closed, however,
pre-closing supervision is not provided. This scheme is also incompatible with latched trip
contacts, as a latched contact will short out the opto for greater than the recommended DDO
timer setting of 400ms. If breaker status monitoring is required a further 1 or 2 opto inputs
must be used. Note: a 52a CB auxiliary contact follows the CB position and a 52b contact is
the opposite.
When the breaker is closed, supervision current passes through the opto input, blocking
diode and trip coil. When the breaker is open current still flows through the opto input and
into the trip coil via the 52b auxiliary contact. Hence, no supervision of the trip path is
provided whilst the breaker is open. Any fault in the trip path will only be detected on CB
closing, after a 400ms delay.
Resistor R1 is an optional resistor that can be fitted to prevent maloperation of the circuit
breaker if the opto input is inadvertently shorted, by limiting the current to <60mA. The
resistor should not be fitted for auxiliary voltage ranges of 30/34 volts or less, as satisfactory
operation can no longer be guaranteed. The table below shows the appropriate resistor
value and voltage setting (OPTO CONFIG. menu) for this scheme.
Summary of Contents for MiCOM P746
Page 4: ......
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 16: ...P746 EN IT G31 Introduction MiCOM P746...
Page 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Page 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Page 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Page 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Page 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Page 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Page 114: ...P746 EN OP G31 Operation MiCOM P746...
Page 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Page 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Page 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Page 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Page 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Page 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Page 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Page 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Page 280: ......
Page 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Page 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Page 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Page 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Page 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Page 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Page 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Page 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Page 438: ......
Page 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Page 468: ......
Page 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Page 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Page 502: ......
Page 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Page 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Page 529: ......