Settings
P746/EN
ST/G31
MiCOM P746
(ST) 4-
13
ST
1.2.6
Circuit Breaker Fail and undercurrent fonction
This function consists of two-stage circuit breaker fail functions that can be initiated by:
•
Internal protection element initiation.
•
External protection element initiation.
For current-based protection, the reset condition is based on undercurrent operation to
determine that the CB has opened. For the non-current based protection, the reset criteria
may be selected by means of a setting for determining a CB Failure condition.
It is common practice to use low set undercurrent elements in protection relays to indicate
that circuit breaker poles have interrupted the fault or load current, as required.
Setting Range
Menu Text
Default Setting
Min. Max.
Step Size
CB FAIL & I<
BREAKER FAIL
CBF Control by
I< and 52a
52a / I< / I< and 52a
Setting which determines the elements that will reset the circuit breaker fail time protection
function.
Both means that 52a and current criteria have to indicate open to reset the CB fail.
I< Current Set
5.000 %
5.000 %
400.0 %
1.000 %
If “CBF Control by” “I<” or “I> and 52a”: setting that determines the circuit breaker fail timer
reset current for overcurrent based protection circuit breaker fail initiation
CB Fail 1 Timer
50.00 ms
0.000 s
10.00 s
10.00 ms
Setting for the circuit breaker fail timer stage 1 for which the initiating condition must be
valid.
CB Fail 2 Timer
200.0 ms
40.00 ms
10.00 s
10.00 ms
Setting to enable or disable the second stage of the circuit breaker function.
CB Fail 3 Timer
50.00 ms
0.000 s
10.00 s
10.00 ms
Setting to enable or disable the third stage of the circuit breaker function.
CB Fail 4 Timer
200.0 ms
40.00 ms
10.00 s
10.00 ms
Setting to enable or disable the fourth stage of the circuit breaker function.
I> Status
Disabled
Disabled / Enabled
To enable (activate) or disable (turn off) the overcurrent check
I> Current Set
120.0 %
5.000 %
400.0 %
1.000 %
If “I> Status” is enabled, pick-up setting for overcurrent element
1.2.7 Supervision
Setting Range
Menu Text
Default Setting
Min. Max.
Step Size
SUPERVISION
VT SUPERVISION
VTS Status
Blocking
Blocking / indication
Sets Voltage Transformer Supervision (VTS) operation.
The relay respond as follows, on operation of any VTS element: VTS set to provide alarm
indication only or blocking of voltage dependent protection elements.
Summary of Contents for MiCOM P746
Page 4: ......
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 16: ...P746 EN IT G31 Introduction MiCOM P746...
Page 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Page 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Page 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Page 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Page 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Page 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Page 114: ...P746 EN OP G31 Operation MiCOM P746...
Page 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Page 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Page 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Page 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Page 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Page 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Page 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Page 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Page 280: ......
Page 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Page 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Page 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Page 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Page 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Page 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Page 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Page 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Page 438: ......
Page 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Page 468: ......
Page 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Page 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Page 502: ......
Page 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Page 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Page 529: ......