6. Alarm Activation
6-4 External output operation
99 / 168
<Gas concentration and external output example (with standard range)>
<4 - 20 mA specification (maintenance output: 2.5 mA setting)>
CAUTION
The 4 - 20 mA output is already adjusted. When the full scale is exceeded, the output will not exceed
approximately 20.5 mA.
If the inhibit function is enabled or initialization is underway, the output follows the 4 - 20 mA output setting
in maintenance mode. Special care is required when starting the product or after altering specifications.
Make sure you fully understand the operation details. Take appropriate precautions where necessary to
prevent false alarms on the receiving side.
When the suppression function is canceled, the signal will be linearly output to 4 mA (equivalent to
0 %LEL).
When the minus suppression function is canceled, the signal will be linearly output to 3.2 mA (equivalent
to −5 %LEL).
Detection mode
Maintenance mode
External output
20.5 mA
20 mA
4 mA
2.5 mA
0
Full scale
20 mA output
Gas concentration
Zero suppression
Full scale over
20.5 mA fixed output