RMV-HFC
vers 0.1
(sw 0.21)
IS RMV-HFC vers 0.1 (sw0.21) 1907
1
SE
Instruktioner
GB
Instructions
D
Anleitungen
ES
Instrucciones
FR
Instructions
Kopplingsschema / Wiring diagram / Schaltplan
/ Diagrama del cableado / Schéma de câblage
Logikmatris / Logical matrix / Logikmatrix / Matriz lógica / Matrice logique
Status
Relay
LED
Buzzer
Power off
Off
Off
Warm-up (5 minutes)
Flashing Green/Red (1 Hz)
Off
Normal operation
Constant Green
Off
Sensor fault
Flashing Red (1 Hz) + one (1)
Amber flash per minute
Pulses 1 / minute
Indications and alarms as gas concentration increases:
(B)
≥1000ppm & >2 seconds & <30 minutes
Flashing Red (2 Hz)
Off
(B)
≥1000ppm & >30 minutes
Flashing Red/Amber (2 Hz)
Pulses (2 Hz)
(A)
≥4000ppm & >30 seconds
Flashing Red/Amber (4 Hz)
Pulses (4 Hz)
Auto Reset:
After 60 seconds delay
Constant Green
Off
For testing
– use gas concentration <(B) ppm
(C)
≥300ppm & >2 seconds
Flashing Green (2 Hz)
Off
1
4
3
2