6. Alarm Activation
6-4 External output operation
104 / 168
<Gas concentration and external output example>
0 - 25 vol% (oxygen deficiency alarm specification)
CAUTION
The 4 - 20 mA output is already adjusted. When the full scale is exceeded, the output will not exceed
approximately 20.5 mA.
If the inhibit function is enabled or initialization is underway, the output follows the 4 - 20 mA output setting
in maintenance mode. Special care is required when starting the product or after altering specifications.
Make sure you fully understand the operation details. Take appropriate precautions where necessary to
prevent false alarms on the receiving side.
When the minus suppression function is canceled, the signal will be linearly output to 3.2 mA (equivalent
to −5 %LEL).
External output
20.5 mA
20 mA
17.4 mA
4 mA
0
Gas concentration
Full scale
20 mA output
Suppression value
Detection mode
Maintenance mode
Full scale over
20.5 mA fixed output
Summary of Contents for GD-3EC
Page 169: ...11 Appendix Revision History 169 168...
Page 170: ...11 Appendix Revision History 170 168...
Page 171: ...11 Appendix Revision History 171 168...
Page 172: ...11 Appendix Revision History 172 168...
Page 173: ...11 Appendix Revision History 173 168...
Page 174: ...11 Appendix Revision History 174 168...
Page 175: ...11 Appendix Revision History 175 168...