7. Maintenance
7-3 Performing tests (test mode)
113 / 168
7-3-2 Performing alarm test
Test to check whether an alarm is triggered when the reading reaches the alarm setpoint.
WARNING
Depending on the settings, contact and gas concentration outputs may be activated during alarm testing,
even in maintenance mode. Take care during alarm testing.
NOTE
The procedure in step 3 is required even if the product is a no alarm relay model. Note that the contact
will not operate even when [on] is selected.
1 Press the ▲ or ▼ key in maintenance mode several times
to select [2-0], then press the SET key.
2 Press the ▲ or ▼ key to select [2-0.1], then press the SET
key.
3 Press the ▲ or ▼ key to select [oFF] or [on], then press the
SET key.
Select [on] if the setting for the contact used is alarm only or
alarm or fault, or [oFF] if the setting is other than those.
4 Press the ▲ or ▼ key to increase or decrease the reading.