6. Alarm Activation
6-4 External output operation
98 / 168
6-4 External output operation
6-4-1 For target gases other than oxygen
Mode
4 - 20 mA (output value)
1
Power supply off
0 mA
2
Initialization
2.5 mA setting: 2.5 mA
4 mA, HOLD, 4 - 20 mA setting: 4 mA
3
Detection mode (no alarm)
4 - 20 mA (concentration output)
4
Detection mode (gas alarm)
4 - 20 mA (concentration output)
5
Detection mode (full scale exceeded)
20.5 mA (fixed)
6
Outside operating temperature range
4 - 20 mA (concentration output)
7
Fault alarm
0.5 mA (fixed)
8
Inhibit
2.5 mA setting: 2.5 mA
4 mA, HOLD, 4 - 20 mA setting: 4 mA
9
Alarm test mode
Output ON setting: 4 - 20 mA (concentration output)
Output OFF setting: 4 mA
10
User mode
2.5 mA setting: 2.5 mA
4 mA setting: 4 mA
HOLD setting: Retains previous value.
4 - 20 mA setting: 4 - 20 mA (concentration output)
11
Maintenance mode
2.5 mA setting: 2.5 mA
4 mA setting: 4 mA
HOLD setting: Retains previous value.
4 - 20 mA setting: 4 - 20 mA (concentration output)
Summary of Contents for GD-3EC
Page 169: ...11 Appendix Revision History 169 168...
Page 170: ...11 Appendix Revision History 170 168...
Page 171: ...11 Appendix Revision History 171 168...
Page 172: ...11 Appendix Revision History 172 168...
Page 173: ...11 Appendix Revision History 173 168...
Page 174: ...11 Appendix Revision History 174 168...
Page 175: ...11 Appendix Revision History 175 168...